background image

Logic Functions - Book 2

SUPERVISORY MESSAGE BLOCK

8-83

13

Fail (FAIL) .......................................................................................................................... – WR
Specifies whether the transaction has failed to complete successfully.

NO

0

Transaction did not fail and completed successfully.

YES

1

Transaction failed.

14

Fail Quality (FAILQ) .......................................................................................................... – WR
This status indicates if the quality of the Fail field is GOOD or BAD.

GOOD

0

Quality when this block (or its controlling loop) is RUN or HOLD.

BAD

1

Quality when this block (or its controlling loop) is OFF.

15

Maximum time allowed for message transaction (RTIME) ...........................................CWR
Time allotted before a message transaction is timed out.

NONE

No timeout (infinite). Not recommended.

msec-time

Specifies the maximum time allowed before the message transaction is timed

out. A setting of 0:0:0.000 implies no timeout (infinite - not
recommended).

16

Maximum number of retries before failure (RETRY)......................................................CWR
Specifies the number of times to retry (0 - 255) if a failure is encountered.

17

Message Code (CODE)..................................................................................................... – WR
This field indicates the message code of the last transaction attempted. This field is only
writeable in the DEBUG state.

No value

0

Response message has not yet been received.

Acknowledgement

1

Message transaction was successful.

Timeout

2

Message transaction was not completed within
the configured timeout value.

Not configuring source

3

Configuration write failure because no longer
authorized to be configuring source.

Service manual

4

Message not accepted because destination
instrument was in service manual mode.

Main data base invalid

5

Message not accepted since the main database
is invalid.

Invalid block

6

Message not accepted because destination LSP
(the block code) is not known by the destination
instrument.

Source not authorized

7

Message not accepted because the destination
LOOP or instrument is under control by a
different source.

Previous Shutdown fault

8

Message not accepted because there was a
previous shutdown fault that must be acknowl-
edged before the message can be accepted.

Invalid attribute

11

Message not accepted because destination LSP
(the attribute) is not known by the destination
instrument.