Error Codes
(revised 5-25-2009)
Code Number
Description
Correction
Warnings
0001
Serial number not present
Hardware serial number has become inoperative – system performance will not be
influenced.
0010
Signal Strength is below Signal Strength Cutoff entry
Low signal strength is typically caused by one of the following:
» Empty pipe
» Improper programming/incorrect values
» Improper transducer spacing
» Non-homogeneous pipe wall
0011
Measured Speed of Sound in the liquid is greater than ±10% different
than the value entered during meter setup
Verify that the correct liquid was selected in the BASIC menu.
Verify that pipe size parameters are correct
Class C Errors
1001
System tables have changed
Initiate a meter RESET by cycling power or by selecting SYSTEM RESET in the SEC
MENU.
1002
System configuration has changed
Initiate a meter RESET by cycling power or by selecting SYSTEM RESET in the SEC
MENU.
Class B Errors
3001
Invalid hardware configuration
Upload corrected file
3002
Invalid system configuration
Upload corrected file
3003
Invalid strategy file
Upload corrected file
3004
Invalid calibration data
Re-calibrate the system
3005
Invalid speed of sound calibration data
Upload new data
3006
Bad system tables
Upload new table data
Class A Errors
4001
Flash memory full
Return unit to factory for evaluation
Table A-5.1 - Error Codes