BACnet® Object Support

Nine BACnet standard objects are supported, a Device object (DEx), a Binary Output
object (BO1), and seven Analog Input objects (AI1 through AI7). The BACnet/IP UDP
port defaults to 0xBAC0. The Object Identifier (BACnet Device ID) and Location can
both be modified through the web page interface.

DEx

Object_Identifier

Defaults to DEx
Can modify “x” through web page (1-9999)

W

Object_Name

Up to 32 characters

W

Object_Type

DEVICE (8)

R

System_Status

OPERATIONAL or NON_OPERATIONAL

R

Vendor_Name

“Racine Federated Inc.”

R

Vendor_Identifier

306

R

Model_Name

“D(X)TFX”

R

Application_Software_

Version

“1.07”

R

Location

“Sample Device Location”
Up to 64 characters - can modify through

web page

W

Protocol_Version

1

R

Protocol_Revision

2

R

Protocol_Services_

Supported

{ readProperty, writeProperty,

readPropertyMultiple,

writePropertyMultiple,

deviceCommunicationControl, who-Has,

who-Is }

R

Protocol_Object_Types_

Supported

{ AnalogInput, BinaryOutput, Device }

R

Object_List

DEx, AI1, AI2, AI3, AI4, AI5, AI6, AI7, BO1

R

Max_APDU_Length_

Accepted

1476

R

Segmentation_Supported 3 – NONE

R

APDU_Timeout

3000 default

R

Number_Of_APDU_

Retries

1 default

R

Device_Address_Binding

always empty

R

Database_Revision

0

R

Table A-3.6 - BACnet® Standard Objects