Installation guide – Veris Industries FSRxxxx SERIES Install User Manual
Page 43
FSRxxxx SERIES
Z205739-0D
PAGE 43
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
05131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
BACnet® Protocol Implementation Conformance Statement
Date:
3-February
2009
Vendor Name:
Racine Federated, Inc.
Product Name:
D(X)TFX
Product Model Number:
DD(X)TFXn-nN-nEn-nn
Applications Software Version: 1.07
Firmware Revision:
N/A
BACnet Protocol Version:
1
BACnet Protocol Revision:
2
Product Description:
Clamp-on ultrasonic flow and energy meters for liquids
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B, DS-WP-B, DS-WPM-B, DM-DDB-B, DM-DOB-B and DM-
DCC-B
BSegmentation Capability: None
Standard Object Types Supported:
Device Object, Analog Input Object, Binary Output Object
Data Link Layer Options:
MS/TP master (Clause 9), baud rate(s): 9600
Device Address Binding:
No
Networking
Options: n/a
Character Sets Supported:
ANSI X3.4
Non-BACnet networks that the gateway supports: n/a