Micro Split-Core Current Switch,
Adjustable Trip Point
Installer’s Specifications
Amperage Range
0.75 to 50 A Continuous
Setpoint
Adjustable
Sensor Supply Voltage
Induced from monitored conductor
Insulation Class
600 VAC RMS (UL), 300 VAC RMS (CE), insulated conductors only
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Frequency
50/60 Hz
Status Output Ratings
N.O. 1.0 A@30 VAC/DC, not polarity sensitive
Off State Resistance
Open switch represents 1+ MΩ of resistance
Terminal Block AWG Range
16-22 AWG
Terminal Block Torque Range
7 in-lb
Agency Approvals
UL508, E150462
Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2010,
Installation Category III or equivalent. The product design provides for functional insulation only.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
WIRING EXAMPLE
H308
TM
308
DIMENSIONS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the product at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller (solid-state
contact).
4. Snap the sensor over the wire to be monitored and push the latch until it is
securely closed. Clip the assembly to the mounting bracket.
5. Calibrate the current switch (see Calibration section).
6. Secure enclosure and reconnect power.
POWER
SOURCE
POWER
SOURCE
BUILDING AUTOMATION
Insulated Conductor ONLY
CONTROLLER
UNIT VENT HEATER
DI
DI
Removable Mounting Bracket
0.3”
(8 mm)
6 AWG max.
1.6”
(40 mm)
1.5”
(38 mm)
0.6”
(15 mm)
1.8”
(46 mm)
Ø 0.18” (x2)
(5 mm)
Setpoint
adjustment
screw here
US Patent 7,193,428
(other patents pending)
RoHS
Compliant