SPECIFICATIONS
Wiring
22 AWG; 2-wire: RTD/Thermistor
Probe
Stainless Steel
Linitemp:
Input Power
5 to 30VDC
Output
1µA/°C or 10mV/°C
Operating Temperature
Probe: -25° to 105°C (-13° to 221°F); Wiring: up to 75°C (167°F)
Resistive:
RTD/Thermistor
See table, facing page
Accuracy:
Calibration Error
1.5°C (2.7°F) typical; 2.5°C (4.5°F) max. at 25°C (77°F)*
Error over Temperature
1.8°C (3.24°F) typical; 3.0°C (5.4°F) max. over 0° to 70°C (32° to 158°F) range;
2.0°C (3.6°F) typical, 3.5°C (6.3°F) max. over -25° to 105°C (-13° to 221°F) range
Increased cable length affects the readings of lower resistance RTDs (100R platinum, RTD).
* Room temperature error documented on each unit.
VAV Discharge Air Sensor For
Reheat Applications
VAV Discharge
Temperature Sensors
DESCRIPTION
The TJ Series temperature sensors are highly accurate and cost effective, with
trouble-free installation. The sensor is encased in a sturdy corrosion-resistant
stainless steel probe. A variety of RTD/thermistor sensor and probe length options
are available for maximum versatility in applications.
APPLICATIONS
●
VAV reheat boxes
●
Dual duct boxes
●
Fan coils
●
Prove that the hot water valve or electric heat is functioning properly
●
Check individual reheating stages
●
Check for hot water valve leaks
●
Determine if damper actuators are functioning on dual duct boxes
FEATURES
●
Stainless steel duct probe with mounting flange...quick, easy installation
●
5’ (1.5 m) plenum rated cable standard...eliminates need to splice
●
4” or 8” (102 mm or 204 mm) duct probes for application flexibility
●
2-wire installation (optional quick disconnect)...installs in just a few
short minutes
●
Installation ready for VAV systems and plenum areas...saves money on job
commissioning and warranty service
TJ