Veris Industries H84xx Install User Manual
H84xx, Notice, Danger
Z204046-0J
PAGE 1
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
12115
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
POWER MONITORING
INSTALLATION GUIDE
H84xx
Power Meters For Use With 1V CTs
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
QUICK INSTALL
1. Mount the device in a fire/electrical enclosure. Use the retaining clips for the
H84xx-V. Use appropriate wall-mounting screws for the H84xx-VB(S).
2. Wire the device. See the Wiring Diagrams section for options.
3. Configure the communications parameters.
Installer’s Specifications
Electrical Characteristics:
Type of measurement
True RMS up to the 15th harmonic. On three-phase AC system
Measurement Accuracy:
Current & Voltage
ANSI C12.16, 0.5%
Power
ANSI C12.16, 1%
Frequency
±-0.01 Hz from 45 to 65 Hz
Data Update Rate
1 sec
Input Voltage Characteristics:
Measured Voltage Max.
UL to 600VAC (L-L); CE to 300VAC (L-N)
Metering Over-Range +20%
Impedance
2 MΩ (L-L)/ 1MΩ (L-N)
Frequency Range
45 to 65 Hz
Input Current Characteristics:
CT Scaling
Primary: Adjustable from 5A to 32,767A
Measurement Input Range
0 to 1.0VAC (+20% over-range)
Impedance
100 kΩ
Control Power*
AC: 100 to 415 ±10%VAC, 5VA; DC: 125 to 250 ±20%VDC, 3W
(see * for 600V option)
Control Power Ride Through Time
100 mS at 120VAC
Output:
Pulse Output #1 H8453V/VB, H8463V/VB
(kWh) N.O., static output
(240VAC or 300VDC, 100mA max. at 25°C,
derate
0.56mA per °C above 25°C) 2.41kV RMS isolation
Pulse Output #2 H8453V/VB
(Phase Detect or kVARh) N.O., static output
(240VAC or 300VDC, 100mA max. at 25°C,
derate
0.56mA per °C above 25°C) 2.41kV RMS isolation
Pulse Output #2 H8463V/VB
(Phase Detect or kVARh) N.C., static output
(240VAC
or 300VDC, 100mA max. at 25°C,
derate
0.56mA per °C above 25°C) 2.41kV RMS isolation
RS485 Port; H8436V/VB; H8437V/VB
2-wire, 2400 to 19200 baud, Modbus RTU
Mechanical Characteristics:
Weight
H8400V=0.81lb; H8400VB=6.35lb; H8400VBS=9.15lb
IP Degree of Protection (IEC 60529)
IP40 front display, meter body IP30 for VB
Display Characteristics
Back-lit green LCD (6 lines total, 4 concurrent values)
Environmental Conditions:
Operating Temperature
Meter: 0° to 60°C; Display: -10° to 50°C
Storage Temperature
Meter and Display: -40° to 85°C
Humidity Range
5 to 95% RH at 50°C (non-condensing)
Metering Category:
North America
CAT III; for distribution systems up to 347V L-N/600VAC L-L
CE
CAT III; for distribution systems up to 300V L-N/480VAC L-L
Dielectric Withstand
Per UL 508, EN61010
Conducted and Radiated Emissions
FCC part 15 Class B, EN55011
Safety:
North America UL508/C22.2
Europe
CE per IEC 61010
*For control voltages >415VAC order H84xxVBS