Installation guide – Veris Industries FSRxxxx SERIES Install User Manual
Page 27
FSRxxxx SERIES
Z205739-0D
PAGE 27
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
05131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
DSP Menu -- Display Menu
The DISPLAY menu parameters control what is shown on the display and the rate at
which displayed items alternate (dwell time).
1. Display Submenu -- Display Options
DISPLAY -- Display (Choice): FLOW, TOTAL, BOTH
With the DISPLAY set to FLOW, the meter only displays the flow rate. When set
to TOTAL, the meter only displays the total flow. By selecting BOTH, the display
alternates between FLOW and TOTAL at the interval selected in SCN DWL (see below).
2. Total Submenu -- Totalizer Choices
TOTAL -- Totalizer Options (Choice): POS - Positive Flow Only, NEG - Negative Flow
Only, NET - Net Flow, BATCH - Batch Mode
Select POS to view the positive direction total only. Select NEG to view the negative
direction total only. Select NET to display the net difference between the positive
direction and negative direction totals. Select the BATCH to configure the totalizer to
count up to a value that is entered as BTCH MUL. After reaching the BTCH MUL value,
the display returns to zero and repeats counting to the BTCH MUL value.
3. Display Dwell Time
SCN DWL -- Dwell Time (Value): 1 to 10 (in Seconds)
Adjustment of SCN DWL sets the time interval for the display to cycle between flow
rate and total flow when the DISPLAY value is set to BOTH. This adjustment range is
from 1 second to 10 seconds.
4. Totalizer Batch Quantity
BTCH MUL -- Batch Multiplier (Value)
If BATCH was chosen for the totalizer mode, enter a value for batch accumulation. This
is the value to which the totalizer accumulates before actuating the control output
pulse and repeating the accumulation. This value includes any exponents that were
entered in the BSC MENU as TOTAL E.
For example:
1) If BTCH MUL is set to 1000, RATE UNT to LITERS and TOTL E to E0 (liters ×
1), then the batch totalizer accumulates to 1000 liters, returns to zero and
repeats indefinitely. The totalizer increments 1 count for every 1 liter that has
passed.
2) If BTCH MUL is set to 1000, RATE UNT to LITERS and TOTL E to E2 (liters ×
100), then the batch totalizer accumulates to 100,000 liters, returns to zero
and repeats indefinitely. The totalizer only increments 1 count for every 100
liters that has passed.