Installation guide – Veris Industries FSRxxxx SERIES Install User Manual
Page 21

FSRxxxx SERIES
Z205739-0D
PAGE 21
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
05131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
18. Fluid Specific Gravity
SP GRAVTY -- Fluid Specific Gravity Entry (Value): Unitless Value
Allows adjustments to be made to the specific gravity (density relative to water) of
the liquid.
As stated previously in the FLUID VI section, specific gravity is utilized in the Reynolds
correction algorithm. It is also utilized if mass flow measurement units are selected
for rate or total.
If a fluid was chosen from the FL TYPE list, a nominal value for specific gravity in that
media is automatically loaded. Revise this value as needed for a given application.
If OTHER was chosen as FL TYPE, a SP GRVTY may need to be entered if mass flows
are to be calculated. A list of alternate fluids and their associated specific gravities is
located in the Appendix of this manual.
19. Fluid Specific Heat Capacity
SP HEAT -- Fluid Specific Heat Capacity (Value): BTU/lb
Allows adjustments to be made to the specific heat capacity of the liquid.
If a fluid was chosen from the FL TYPE list, a default specific heat will be
automatically loaded. This default value is displayed as SP HEAT in the BSC MENU. If
the actual specific heat of the liquid is known or it differs from the default value, the
value can be revised. See Tables 4.1, 4.2, and 4.3 for specific values. Enter a value that
is the mean of both pipes.
Specific Heat Capacity of Water
Temperature
Specific Heat
(BTU/lb °F)
°F
°C
32-212
0-100
1.00
250
121
1.02
300
149
1.03
350
177
1.05
Table 4.1 - Specific Heat Capacity Values for Water
Specific Heat Capacity of Common Fluids
Fluid
Temperature
Specific Heat
(BTU/lb °F)
°F
°C
Ethanol
32
0
0.65
Methanol
54
12
0.60
Brine
32
0
0.71
Brine
60
15
0.72
Sea Water
63
17
0.94
Table 4.2 - Specific Heat Capacity Values for Other Common Fluids
Specific Heat Capacity (BTU/lb °F)
Temperature
Ethylene Glycol Solution (% by volume)
°F
°C
25
30
40
50
60
65
100
-40
-40
n/a
n/a
n/a
n/a
0.68
0.70
n/a
0
-1708
n/a
n/a
0.83
0.78
0.72
0.70
0.54
40
4.4
0.91
0.89
0.845
0.80
0.75
0.72
0.56
80
26.7
0.92
0.90
0.86
0.82
0.77
0.74
0.59
120
84.9
0.93
0.92
0.88
0.83
0.79
0.77
0.61
160
71.1
0.94
0.93
0.89
0.85
0.81
0.79
0.64
200
93.3
0.95
0.94
0.91
0.87
0.83
0.81
0.66
240
115.6
n/a
n/a
n/a
n/a
n/a
0.83
0.69
Table 4.3 - Specific Heat Capacity Values for Ethylene Glycol/Water
20. Transducer Spacing
XDC SPAC -- Transducer Spacing Calculation (Value): ENGLSH (Inches), METRIC
(Millimeters)
Note: This value is calculated by the firmware after all pipe parameters have been entered. The
spacing value only pertains to FST4 and FST5 transducer sets.
This value represents the one-dimensional linear measurement between the
transducers (the upstream/downstream measurement that runs parallel to the pipe).
This value is in inches if ENGLSH was selected as UNITS; in millimeters if METRIC was
selected. This measurement is taken between the lines scribed into the side of the
transducer blocks.
21. Rate Units
RATE UNT -- Engineering Units for Flow Rate (Choice)
Gallons
Gallons
Pounds
LB
Liters
Liters
Kilograms
KG
Millions of gallons MGal
BTUs
BTU
Cubic feet
Cubic Ft
Thousands of BTUs MBTU
Cubic meters
Cubic Me
Millions of BTUs
MMBTU
Acre feet
Acre Ft
Tons
TON
Oil barrels
Oil Barr [42 Gallons]
Kilojoule
kJ
Liquid barrels
Liq Barr [31.5 Gallons] Kilowatt
kW
Feet
Feet
Megawatt
MW
Meters
Meters
Select a desired engineering unit for flow rate measurements.
22. Rate Interval
RATE INT -- Time Interval for Flow Rate (Choice): SEC (Seconds), MIN (Minutes), HOUR
(Hours), DAY (Days)
Select a desired engineering unit for flow rate measurements.