Troubleshooting
6-12
Controller on page 5-21). The controllers will stop boot-up to show 
messages on the LCD. The messages and corresponding resolutions are 
the same as failure of replacement controller.
If the two controllers have different versions of boot code or firmware, you 
need to choose between the versions. If the two controllers have different 
BBM option, you need to choose to enable or disable it. If ENC SN UNEQ is 
displayed, the two controllers came from different chassis, and you need 
to boot up first with only one controller as the master controller, and install 
the other controller later.
3. Host computer reports I/O errors during path/
controller failover
If you use MPIO against path or controller failure, it is essential to check if 
your MPIO driver is installed properly. Below are the checking items you 
need to do:
• A virtual disk has been mapped to LUNs of all host-interface ports in
simple storage presentation configuration. Or, a virtual disk has been 
mapped to a host or host group in symmetric storage presentation 
configuration.
• Because a LUN is not accessible during regular initialization. Install the
MPIO driver after the regular initialization of a virtual disk is done, or 
use background initialization.
• All cables are connected and the corresponding paths are
displayed by the MPIO software utility.
• Check the device nodes from the operating system disk
management utility to make sure the MPIO devices have been 
created. Make sure the number of MPIO devices matches your 
cabling topology (see 5.1 Multi-Path IO Solutions on page 5-1 for 
how to calculate the number).
4. The replacement controller cannot work for controller fail
back
The replacement controller stops boot-up if it fails to discover the same 
set of expansion chassis of the surviving controller. You need to make sure 
the expansion chassis are properly attached to the expansion port of the 
replacement controller and there is no broken connection between the 
expansion chassis. Please also note that the I/O access and background 
tasks can be migrated to the replacement controller only after the host-
interfaces of the replacement controller are properly connected to the 
host computers.