Sitrans p measuring instruments for pressure – Siemens SITRANS P User Manual
Page 98
SITRANS P measuring instruments for pressure
Transmitters for gage, absolute and differential pressure, flow and level
DS III series for absolute pressure
(from differential pressure series)
2/98
Siemens FI 01 · 2009
2
■
Technical specifications
SITRANS P, DS III series for absolute pressure (from differential pressure series)
HART
PROFIBUS PA or FOUNDATION Fieldbus
Input
Measured variable
Absolute pressure pressure
Spans (infinitely adjustable) or
nominal measuring range and
max. permissible working pressure
Span
Maximum working pres-
sure
Nominal measuring
range
Maximum working pres-
sure
8.3 ... 250 mbar a
(0.12 ... 3.6 psi a)
32 bar a
(464 psi a)
250 mbar a
(3.6 psi a)
32 bar a
(464 psi a)
43 ... 1300 mbar a
(0.62 ... 18.9 psi a)
32 bar a
(464 psi a)
1300 bar a
(18.9 psi a)
32 bar a
(464 psi a)
160 ... 5000 mbar a
(2.32 ... 72.5 psi a)
32 bar a
(464 psi a)
5 bar a
(72.5 psi a)
32 bar a
(464 psi a)
1 ... 30 bar a
(14.5 ... 435 psi a)
160 bar a
(2320 psi a)
30 bar a
(435 psi a)
160 bar a
(2320 psi a)
5.3 ... 100 bar a
(77 ... 1450 psi a)
160 bar a
(2320 psi a)
(for connection thread
M10 and
7
/
16
-20 UNF in
the process flanges)
100 bar a
(1450 psi a)
160 bar a
(2320 psi a)
(for connection thread
M10 and
7
/
16
-20 UNF in
the process flanges)
Lower measuring limit
• Measuring cell with silicone oil filling
0 mbar a (0 psi a)
Upper measuring limit
100% of max. span
Output
Output signal
4 ... 20 mA
Digital PROFIBUS PA or FOUNDATION Fieldbus
signal
• Lower limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
-
• Upper limit (infinitely adjustable)
23 mA, factory preset to 20.5 mA or optionally set
to 22.0 mA
-
Load
• Without HART communication
R
B
≤ (U
H
- 10.5 V)/0.023 A in
Ω,
U
H
: Power supply in V
-
• With HART communication
R
B
= 230 ... 500
Ω (SIMATIC PDM) or
R
B
= 230 ... 1100
Ω (HART Communicator)
-
Physical bus
-
IEC 61158-2
With polarity reversal protection
-
Yes
Accuracy
To EN 60770-1
Reference conditions
(All error data refer always refer to the set
span)
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling,
room temperature 25 °C (77 °F)) r: Span ratio (r = max. span / set span)
Error in measurement and fixed-point setting
(including hysteresis and repeatability)
• Linear characteristic
≤ 0.1%
- r
≤ 10
≤ 0.1%
- 10 < r
≤ 30
≤ 0.2%
Long-term drift (temperature change
± 30 °C
(
± 54 °F))
≤ (0.1 ⋅ r)%/year
≤ 0.1%/year
Influence of ambient temperature
• at -10 ... +60 °C (14 ... 140 °F)
≤ (0.1 ⋅ r +0.2)%
≤ 0.3%
• at -40 ... -10 °C and +60 ... +85 °C
(-40 ... +14 °F and 140 ... 185 °F)
≤ (0.1 ⋅ r + 0.15)%/10 K
≤ 0.25%/10 K
Measured Value Resolution
-
3
⋅ 10
-5
of nominal measuring range
© Siemens AG 2008