Sitrans p300 with pmc connection, Sitrans p measuring instruments for pressure – Siemens SITRANS P User Manual
Page 58
SITRANS P measuring instruments for pressure
Transmitters for gage pressure for the paper industry
SITRANS P300 with PMC connection
2/58
Siemens FI 01 · 2009
2
■
Technical specifications
SITRANS P300 for gage pressure with PMC connection for the paper industry
HART
PROFIBUS PA
Input
Measured variable
Gage pressure (flush-mounted)
Spans (infinitely adjustable) or
nominal measuring range and
max. permissible test pressure
Span
Max. perm. test pres-
sure
Nominal measuring
range
Max. perm. test pres-
sure
0.01 ... 1 bar g
(0.15 ... 14.5 psi g)
6 bar g
(87 psi g)
1 bar g
(14.5 psi g)
6 bar g
(87 psi g)
0.04 ... 4 bar g
(0.58 ... 58 psi g)
10 bar g
(145 psi g)
4 bar g
(58 psi g)
10 bar g
(145 psi g)
0.16 ... 16 bar g
(2.3 ... 232 psi g)
32 bar g
(464 psi g)
16 bar g
(232 psi g)
32 bar g
(464 psi g)
Depending on the process connection, the span
may differ from these values
Depending on the process connection, the nomi-
nal measuring range may differ from these values
Lower measuring limit
• Measuring cell with silicone oil
100 mbar a (1.45 psi a)
Upper measuring limit
• Measuring cell with silicone oil
100% of max. span
100% of the max. nominal measuring range
Output
Output signal
4 ... 20 mA
Digital PROFIBUS PA signal
Physical bus
-
IEC 61158-2
With polarity reversal protection
No
Yes
Electrical damping T
63
(step width 0.1 s)
Set to 0.1 s (0 ... 100 s)
Accuracy
To EN 60770-1
Reference conditions
(All error data refer always refer to the set
span)
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, measuring cell
with silicone oil, room temperature 25 °C (77 °F), span ratio (r = max. span/set span)
Measurement deviation with cut-off point set-
ting, including hysteresis and repeatability.
Linear characteristic curve
≤ 0,075%
• r
≤ 10
≤ (0.0029 ⋅ r + 0.071)%
• 10 < r
≤ 30
≤ (0.0045 ⋅ r + 0.071)%
• 30 < r
≤ 100
≤ (0.005 ⋅ r + 0.05)%
Settling time T
63
without electrical damping
Approx. 0.2 s
Long-term drift at
±30 °C (±54 °F)
≤ (0.25 ⋅ r)%/5 years
≤ 0.25%/5 years
Influence of ambient temperature
• at -10 ... +60 °C (14 ... 140 °F)
≤ (0.1 ⋅ r + 0.2)%
≤ 0,3%
• at -40 ... -10 °C and +60 ... +85 °C
(-40 ... 14 °F and 140 ... 185 °F)
≤ (0.1 ⋅ r + 0.15)%/10 K
≤ 0.25%/10 K
Influence of the medium temperature (only
with front-flush diaphragm)
• Temperature difference between medium
temperature and ambient temperature
3 mbar/10 K (0.04 psi/10 K)
Rated operating conditions
Installation conditions
Ambient temperature
Observe the temperature class in areas subject to explosion hazard.
• Measuring cell with silicone oil
-40 ... +85 °C (-40 ... +185 °F)
• Digital display
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
Climatic class
Condensation
Permissible
Degree of protection to EN 60529
IP65, IP68, NEMA X, enclosure cleaning, resistant to lyes, steam to 150° C (302 °F)
Electromagnetic compatibility
• Emitted interference and interfer. immunity
To EN 61326 and NAMUR NE 21
© Siemens AG 2008