beautypg.com

Sitrans p measuring instruments for pressure, Ds iii series for level 2/127 – Siemens SITRANS P User Manual

Page 127

background image

SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series

for level

2/127

Siemens FI 01 · 2009

2

HART communication

HART communication

230 ... 1100

Ω

Protocol

HART Version 5.x

Software for computer

SIMATIC PDM

PROFIBUS PA communication

Simultaneous communication with
master class 2 (max.)

4

The address can be set using

Configuration tool or local opera-
tion (standard setting address
126)

Cyclic data usage

• Output byte

5 (one measuring value) or
10 (two measuring values)

• Input byte

0, 1, or 2 (register operating mode
and reset function for metering)

Internal preprocessing

Device profile

PROFIBUS PA Profile for Process
Control Devices Version 3.0,
Class B

Function blocks

2

• Analog input

- Adaptation to customer-specif-

ic process variables

Yes, linearly rising or falling char-
acteristic

- Electrical damping T

63

, adjust-

able

0 ... 100 s

- Simulation function

Input /Output

- Failure mode

Can be parameterized (last good
value, substitute value, incorrect
value)

- Limit monitoring

Yes, one upper and lower warning
limit and one alarm limit respec-
tively

• Register (totalizer)

Can be reset, preset, optional
direction of counting, simulation
function of register output

- Failure mode

Can be parameterized (summation
with last good value, continuous
summation, summation with incor-
rect value)

- Limit monitoring

One upper and lower warning limit
and one alarm limit respectively

• Physical block

1

Transducer blocks

2

• Pressure transducer block

- Can be calibrated by applying

two pressures

Yes

- Monitoring of sensor limits

Yes

- Specification of a container

characteristic with

Max. 30 nodes

- Square-rooted characteristic

for flow measurement

Yes

- Gradual volume suppression

and implementation point of
square-root extraction

Parameterizable

- Simulation function for mea-

sured pressure value and sen-
sor temperature

Constant value or over parameter-
izable ramp function

Communication FOUNDATION Fieldbus

Function blocks

3 function blocks analog input,
1 function block PID

• Analog input

- Adaptation to customer-specif-

ic process variables

Yes, linearly rising or falling char-
acteristic

- Electrical damping T

63

, adjust-

able

0 ... 100 s

- Simulation function

Output/input (can be locked within
the device with a bridge)

- Failure mode

Can be parameterized (last good
value, substitute value, incorrect
value)

- Limit monitoring

Yes, one upper and lower warning
limit and one alarm limit respec-
tively

- Square-rooted characteristic

for flow measurement

Yes

• PID

Standard FF function block

• Physical block

1 Resource block

Transducer blocks

1 transducer block Pressure with
calibration, 1 transducer block
LCD

• Pressure transducer block

- Can be calibrated by applying

two pressures

Yes

- Monitoring of sensor limits

Yes

- Simulation function: Measured

pressure value, sensor temper-
ature and electronics tempera-
ture

Constant value or over parameter-
izable ramp function

Mounting flange

Nom. diam.

Nom. press.

• To EN 1092-1

- DN 80

PN 40

- DN 100

PN16, PN40

• To ASME B16.5

- 3 inch

Class 150, class 300

- 4 inch

Class 150, class 300

© Siemens AG 2008