beautypg.com

Ds iii series with pmc connection, Sitrans p measuring instruments for pressure, Ds iii series with pmc connection 2/52 – Siemens SITRANS P User Manual

Page 52

background image

SITRANS P measuring instruments for pressure

Transmitters for gage pressure for the paper industry

DS III series with PMC connection

2/52

Siemens FI 01 · 2009

2

Technical specifications

SITRANS P, DS III series for gage pressure with PMC connection for the paper industry

HART

PROFIBUS PA or FOUNDATION Fieldbus

Input

Measured variable

Gage pressure

Spans (infinitely adjustable) or
nominal measuring range and
max. permissible test pressure

Span

Max. perm. test pres-
sure

Nominal measuring
range

Max. perm. test pres-
sure

0.01 ... 1 bar g
(0.145 ... 14.5 psi g)

6 bar g
(87 psi g)

1 bar g
(14.5 psi g)

6 bar g
(87 psi g)

0.04 ... 4 bar g
(0.58 ... 58 psi g)

10 bar g
(145 psi g)

4 bar g
(58 psi g)

10 bar g
(145 psi g)

0.16 ... 16 bar g
(2.32 ... 232 psi g)

32 bar g
(464 psi g)

16 bar g
(232 psi g)

32 bar g
(464 psi g)

Lower measuring limit

• Measuring cell with silicone oil filling

100 mbar a (1.45 psi a)

Upper measuring limit

100% of max. span

Output

Output signal

4 ... 20 mA

Digital PROFIBUS PA or FOUNDATION Fieldbus
signal

• Lower limit (infinitely adjustable)

3.55 mA, factory preset to 3.84 mA

-

• Upper limit (infinitely adjustable)

23 mA, factory preset to 20.5 mA or optionally set
to 22.0 mA

-

Load

• Without HART communication

R

B

≤ (U

H

- 10.5 V)/0.023 A in

Ω,

U

H

: Power supply in V

-

• With HART communication

R

B

= 230 ... 500

Ω (SIMATIC PDM) or

R

B

= 230 ... 1100

Ω (HART Communicator)

-

Physical bus

-

IEC 61158-2

With polarity reversal protection

-

Yes

Accuracy

To EN 60770-1

Reference conditions
(All error data refer always refer to the set
span)

Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling,
room temperature 25 °C (77 °F) r: Span ratio (r = max. span/set span)

Error in measurement and fixed-point setting
(including hysteresis and repeatability)

• Linear characteristic

≤ 0,075%

- r

≤ 10

≤ (0.0029 ⋅ r + 0.071)%

- 10 < r

≤ 30

≤ (0.0045 ⋅ r + 0.071)%

- 30 < r

≤ 100

≤ (0.005 ⋅ r + 0.05)%

Long-term drift (temperature change

± 30 °C

(

± 54 °F))

≤ (0.25 ⋅ r)% every 5 years

≤ 0.25% every 5 years

Influence of ambient temperature

• at -10 ... +60 °C (14 ... 140 °F)

≤ (0.08 ⋅ r + 0.1)%

≤ 0,3%

• at -40 ... -10 °C and +60 ... +85 °C

(-40 ... +14 °F and 140 ... 185 °F)

≤ (0.1 ⋅ r + 0.15)%/10 K

≤ 0.25%/10 K

Influence of medium temperature

• Temperature difference between medium

temperature and ambient temperature

3 mbar/10 K (0.04 psi/10 K)

Influence of mounting position

≤ 0.1 mbar g (0.00145 psi g) per 10° inclination

Measured Value Resolution

-

3

⋅ 10

-5

of nominal measuring range

© Siemens AG 2008