Sitrans p measuring instruments for pressure – Siemens SITRANS P User Manual
Page 60
SITRANS P measuring instruments for pressure
Transmitters for gage pressure for the paper industry
SITRANS P300 with PMC connection
2/60
Siemens FI 01 · 2009
2
SITRANS P300 for gage pressure with PMC connection for the
paper industry
HART communication
HART communication
230 ... 1100
Ω
Protocol
HART Version 5.x
Software for computer
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
configuration tool
Local operation
(standard setting Address 126)
Cyclic data usage
• Output byte
One measuring value: 5 bytes
Two measuring values: 10 bytes
• Input byte
Register operating mode: 1 bytes
Reset function due to metering.
1 bytes
Device profile
PROFIBUS PA Profile for Process
Control Devices Version 3.0,
Class B
Function blocks
2
• Analog input
- Adaptation to customer-specific
process variables
Linearly rising or falling character-
istic
- Electrical damping T
63
0 ... 100 s adjustable
- Simulation function
Input /Output
- Limit monitoring
One upper and lower warning limit
and one alarm limit respectively
• Register (totalizer)
Can be reset and preset
Optional direction of counting
Simulation function of the register
output
- Limit monitoring
One upper and lower warning limit
and one alarm limit respectively
• Physical block
1
Transducer blocks
2
• Pressure transducer block
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 31 nodes
- Characteristic
Linear
- Simulation function
Available
• Transducer block "Electronic tem-
perature"
- Simulation function
Available
Communication FOUNDATION Fieldbus
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customer-specif-
ic process variables
Yes, linearly rising or falling char-
acteristic
- Electrical damping T
63
, adjust-
able
0 ... 100 s
- Simulation function
Output/input (can be locked within
the device with a bridge)
- Failure mode
Can be parameterized (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning
limit and one alarm limit respec-
tively
- Square-rooted characteristic
for flow measurement
Yes
• PID
Standard FF function block
• Physical block
1 Resource block
Transducer blocks
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Pressure transducer block
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Simulation function: Measured
pressure value, sensor temper-
ature and electronics tempera-
ture
Constant value or over parameter-
izable ramp function
© Siemens AG 2008