beautypg.com

Sitrans p measuring instruments for pressure, Ds iii series for level 2/126 – Siemens SITRANS P User Manual

Page 126

background image

SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series
for level

2/126

Siemens FI 01 · 2009

2

Certificate and approvals

Classification according to pressure equipment
directive (DRGL 97/23/EC)

For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of Article 3,
paragraph 3 (sound engineering practice)

Explosion protection

• Intrinsic safety "i"

PTB 99 ATEX 2122

- Identification

Ex II 1/2 G EEx ia/ib IIB/IIC T6

- Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +70 °C (-40 ... +158 °F) temperature class T5;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6

- Connection

To certified intrinsically-safe circuits with maxi-
mum values:
U

i

= 30 V, I

i

= 100 mA,

P

i

= 750 mW; R

i

= 300

Ω

FISCO supply unit:
U

o

= 17.5 V, I

o

= 380 mA, P

o

= 5.32 W

Linear barrier:
U

o

= 24 V, I

o

= 250 mA, P

o

= 1.2 W

- Effective internal inductance/capacitance

L

i

= 0.4 mH, C

i

= 6 nF

L

i

= 7

μH, C

i

= 1.1 nF

• Explosion-proof "d"

PTB 99 ATEX 1160

- Identification

Ex II 1/2 G EEx d IIC T4/T6

- Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6

- Connection

To circuits with values: U

H

= 10.5 ... 45 V DC

To circuits with values: U

H

= 9 ... 32 V DC

• Dust explosion protection for zone 20

PTB 01 ATEX 2055

- Identification

Ex II 1 D IP65 T 120 °C
Ex II 1/2 D IP65 T 120 °C

- Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F)

- Max.surface temperature

120 °C (248 °F)

- Connection

To certified intrinsically-safe circuits with maxi-
mum values:
U

i

= 30 V, I

i

= 100 mA,

P

i

= 750 mW, R

i

= 300

Ω

FISCO supply unit:
U

o

= 17.5 V, I

o

= 380 mA, P

o

= 5.32 W

Linear barrier:
U

o

= 24 V, I

o

= 250 mA, P

o

= 1.2 W

- Effective internal inductance/capacitance

L

i

= 0.4 mH, C

i

= 6 nF

L

i

= 7

μH, C

i

= 1.1 nF

• Dust explosion protection for zone 21/22

PTB 01 ATEX 2055

- Identification

Ex II 2 D IP65 T 120 °C

- Connection

To circuits with values: U

H

= 10.5 ... 45 V DC;

P

max

= 1.2 W

To circuits with values: U

H

= 9 ... 32 V DC;

P

max

= 1.2 W

• Type of protection "n" (zone 2)

TÜV 01 ATEX 1696 X

Planned

- Identification

Ex II 3 G EEx nA L IIC T4/T5/T6

-

• Explosion protection to FM

Certificate of Compliance 3008490

- Identification (XP/DIP) or (IS); (NI)

CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I,
DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

• Explosion protection to CSA

Certificate of Compliance 1153651

- Identification (XP/DIP) or (IS)

CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD
T4...T6; CL II, DIV 2, GP FG; CL III

SITRANS P, DS III series for level

HART

PROFIBUS PA or FOUNDATION Fieldbus

© Siemens AG 2008