SITRANS P measuring instruments for pressure

Remote seals

Measuring setups with remote seals

2/183

Siemens FI 01 · 2009

2

Dimensional drawings

Types of installation for pressure and level measurements (open vessels)

Types of installation for absolute level measurements (closed vessels)

Type of installation for differential pressure and flow measurements

H

1

H

1

H

U

DH

H

O

H

U

DH

H

O

Installation type A
Start-of-scale: p

MA

= r

FL

· g · H

U

- r

Oil

· g · H

1

Full-scale:

p

ME

= r

FL

· g · H

O

- r

Oil

· g · H

1

Installation type B
Start-of-scale: p

MA

= r

FL

· g · H

U

+ r

Oil

· g · H

1

Full-scale:

p

ME

= r

FL

· g · H

O

+ r

Oil

· g · H

1

Legend
p

MA

Start-of-scale value to be set

p

ME

Full-scale value to be set

r

FL

Density of medium in vessel

r

Oil

Density of filling oil in the capillary to

the remote seal

g

Local acceleration due to gravity

H

U

Start-of-scale value

H

O

Full-scale value

H

1

Distance between vessel flange and pressure trans.

Pressure transmitter

above the measuring point

Pressure transmitter

below the measuring point

H

1

£ 7 m (23 ft), with halocarbon oil as filling liquid only H

1

£ 4 m (13.1 ft)

Installation type A

Installation type B

Installation type C

1

and C

2

Start-of-scale: p

MA

= p

START

+ r

Oil

· g · H

1

Full-scale:

p

ME

= p

END

+ r

Oil

· g · H

1

Legend
p

MA

Start-of-scale value to be set

p

ME

Full-scale value to be set

p

START

Start-of-scale value

p

END

Full-scale value

r

Oil

Density of filling oil in the capillary to

the remote seal

g

Local acceleration due to gravity

H

1

Distance between vessel flange and pressure trans.

H

1

H

1

p

abs

p

abs

Pressure transmitter for absolute pressure always below the measuring point: H

1

³ 200 mm (7.9 inch)

Installation type C

1

Installation type C

2

H

2

H

V

H

1

Installation type D
Start-of-scale: p

MA

= p

START

- r

Oil

· g · H

V

Full-scale:

p

ME

= p

END

- r

Oil

· g · H

V

Legend
p

MA

Start-of-scale value to be set

p

ME

Full-scale value to be set

p

START

Start-of-scale value

p

END

Full-scale value

r

Oil

Density of filling oil in the capillary to

the remote seal

g

Local acceleration due to gravity

H

V

Distance between the measuring points (spigots)

Installation type D

Filter monitoring