Sitrans p measuring instruments for pressure, Diaphragm seals of flange design – Siemens SITRANS P User Manual
Page 169
SITRANS P measuring instruments for pressure
Diaphragm seals of flange design
For differential pressure,
fixed connection and with capillary
2/169
Siemens FI 01 · 2009
2
■
Dimensional drawings
Diaphragm seals of flange design with flexible capillary, fixed connec-
tion, for connection to a SITRANS P pressure transmitter for differential
pressure, dimensions in mm (inch)
Connection to EN 1092-1
Connection to ASME B16.5
d: Inside diameter of gasket according to EN 1092-1 /
ASME B16.5
d
M
: Effective diaphragm diameter
D
+
b
f
n d 2
x
ø
k
M
d
ø
d 4
R
15
0 (5
.9)
>_
100
(3.94)
b
f
n d 2
x
ø
D
ø
k
ø
d 4
ø
d 5
L
Tube length L
see
Ordering data
Nom.
diam.
Nom.
press.
b
D
d
2
d
4
d
5
d
M
f
k
n
mm
mm
mm
mm
mm
mm
mm
mm
DN 80
PN 40 24
200
18
138
76
89
2
160
8
DN 100 PN 16 20
200
18
158
94
89
2
180
8
PN 40 24
235
22
162
94
89
2
190
8
Nom.
diam.
Nom.
press.
b
D
d
2
d
4
d
5
d
M
f
k
n
lb/
sq.in.
mm
mm
mm
mm
mm
mm
mm
mm
(inch) (inch)
(inch) (inch) (inch) (inch) (inch) (inch)
3 inch
150
24
190
20
127
76
89
1,6
152,5
4
(0.96)
(7.48)
(0.79) (5)
(3)
(3.50) (0.06) (6)
300
29
210
22
127
76
89
1,6
168,5
8
(1.14)
(8.27)
(0.87) (5)
(3)
(3.50) (0.06) (6.63)
4 inch
150
24
230
20
158
94
89
1,6
190,5
4
(0.95)
(9.06)
(0.79) (6.22) (3.69) (3.50) (0.06) (7)
300
32
255
22
158
94
89
1,6
200
8
(1.26)
(10.04) (0.87) (6.22) (3.69) (3.50) (0.06) (7.87)
© Siemens AG 2008