For absolute pressure (from gage pressure series), Sitrans p measuring instruments for pressure – Siemens SITRANS P User Manual

Page 89

background image

SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series for absolute pressure

(from gage pressure series)

2/89

Siemens FI 01 · 2009

2

Technical specifications

SITRANS P, DS III series for absolute pressure (from the gage pressure series)

HART

PROFIBUS PA or FOUNDATION Fieldbus

Input

Measured variable

Absolute pressure

Spans (infinitely adjustable) or
nominal measuring range and
max. permissible test pressure

Span

Max. perm. test
pressure

Nominal measuring
range

Max. perm. test
pressure

8.3 ... 250 mbar a
(0.12 ... 3.6 psi a)

6 bar a
(87 psi a)

250 mbar a
(3.6 psi a)

6 bar a
(87 psi a)

43 ... 1300 mbar a
(0.62 ... 18.9 psi a)

10 bar a
(145 psi a)

1300 mbar a
(18.9 psi a)

10 bar a
(145 psi a)

160 ... 5000 mbar a
(2.32 ... 72.5 psi a)

30 bar a
(435 psi a)

5 bar a
(72.5 psi a)

30 bar a
(435 psi a)

1 ... 30 bar a
(14.5 ... 435 psi a)

100 bar a
(1450 psi a)

30 bar a
(435 psi a)

100 bar a
(1450 psi a)

Lower measuring limit

• Measuring cell with silicone oil filling

0 mbar a (0 psi a)

Upper measuring limit

100% of max. span

Output

Output signal

4 ... 20 mA

Digital PROFIBUS PA or FOUNDATION Fieldbus
signal

• Lower limit (infinitely adjustable)

3.55 mA, factory preset to 3.84 mA

-

• Upper limit (infinitely adjustable)

23 mA, factory preset to 20.5 mA or optionally set
to 22.0 mA

-

Load

• Without HART communication

R

B

≤ (U

H

- 10.5 V)/0.023 A in

Ω,

U

H

: Power supply in V

-

• With HART communication

R

B

= 230 ... 500

Ω (SIMATIC PDM) or

R

B

= 230 ... 1100

Ω (HART Communicator)

-

Physical bus

-

IEC 61158-2

With polarity reversal protection

-

Yes

Accuracy

To EN 60770-1

Reference conditions
(All error data refer always refer to the set
span)

Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling,
room temperature 25 °C (77 °F)) r: Span ratio (r = max. span / set span)

Error in measurement and fixed-point setting
(including hysteresis and repeatability)

• Linear characteristic

≤ 0.1%

- r

≤ 10

≤ 0.1%

- 10 < r

≤ 30

≤ 0.2%

Long-term drift (temperature change

±30 °C

(

±54 °F))

≤ (0.1 ⋅ r)%/year

≤ 0.1%/year

Influence of ambient temperature

• at -10 ... +60 °C (14 ... 140 °F)

≤ (0.1 ⋅ r +0.2)%

≤ 0,3%

• at -40 ... -10 °C and +60 ... +85 °C

(-40 ... +14 °F and 140 ... 185 °F)

≤ (0.1 ⋅ r + 0.15)%/10 K

≤ 0.25%/10 K

Measured Value Resolution

-

3

⋅ 10

-5

of nominal measuring range

© Siemens AG 2008