SITRANS P measuring instruments for pressure

Remote seals

Measuring setups without remote seals

2/186

Siemens FI 01 · 2009

2

Measuring setups for closed containers

r

Ho

Hu

Level measurement, Version 1
Start-of-scale: Dp

MA

= r · g · H

U

Full-scale:

Dp

ME

= r · g · H

O

Legend
Dp

MA

Start-of-scale value to be set

Dp

ME

Full-scale value to be set

r

Density of medium in vessel

g

Local acceleration due to gravity

H

U

Start-of-scale value

H

O

Full-scale value

Maximum level

Start-of-scale value

Full-scale value

Transmitter

reference line

Static

pressure

Gas-filled negative

pressure line

Maximum level

H

r

r

r'

Hv

Hu

2

2

1

o

Separation layer measurement
Start-of-scale: Dp

MA

= g · (H

U

· r

1

+ (H

O

- H

U

) · r

2

- H

V

· r'

2

)

Full-scale:

Dp

ME

= g · (H

O

· r

1

- H

V

· r'

2

)

Legend
Dp

MA

Start-of-scale value to be set

Dp

ME

Full-scale value to be set

r

1

Density of heavier liquid with separation layer

in vessel

r

2

Density of lighter liquid with separation layer

r'

2

Density of liquid in the negative pressure line

(corresponding to the temperature existing there)

g

Local acceleration due to gravity

H

U

Start-of-scale value

H

O

Full-scale value

H

V

Distance between the measuring points

(spigots)

Max. separation layer

Start-of-scale value

Full-scale value

Static

pressure

Constant level

Static

pressure

Transmitter

reference line