Please note:

• It is not possible to have a smaller span than the smallest span of the device of the entire device range.

• The value must not fall below the minimum permissible operating pressure of the special measuring range of the selected

measuring cell.

• The required span of the device must lie between the smallest and the largest possible span of the entire device range.

Selection and Ordering data

Order No.

Order code

SITRANS P pressure transmitters for pressure, series Z for gage and absolute pressure
2 or 3-wire system, rising characteristic curve

D)

7 MF 1 5 6 4 -

7 7 7 7 7

-

7 7 7

1

777

Measuring range

perm. working pressure

Burst pressure

Min.

Max.

For gage pressure

with metal measuring cell

0 ... 100 mbar g

(0 ... 1.45 psi g)

-0,6 bar g

(-8.7 psi g)

0,6 bar g

(8.7 psi g)

1 bar g

(14.5 psi g)

}

3 A A 0

0 ... 160 mbar g

(0 ... 2.32 psi g)

-0,6 bar g

(-8.7 psi g)

0,6 bar g

(8.7 psi g)

1 bar g

(14.5 psi g)

}

3 A B 0

0 ... 250 mbar g

(0 ... 3.63 psi g)

-1 bar g

(-14.5 psi g) 1 bar g

(14.5 psi g)

1.7 bar g

(25 psi g)

}

3 A C 0

0 ... 400 mbar g

(0 ... 5.80 psi g)

-1 bar g

(-14.5 psi g) 1 bar g

(14.5 psi g)

1.7 bar g

(25 psi g)

}

3 A D 0

0 ... 600 mbar g

(0 ... 8.70 psi g)

-1 bar g

(-14.5 psi g) 3 bar g

(43.5 psi g)

5 bar g

(72 psi g)

}

3 A G 0

Other version for measuring range < 1 bar (< 14.5 psi g), add Order code and plain text:
measuring range: ... up to ... mbar g (psi g)

1)

9 A C 0

H 1 Y

with ceramic measuring cell

0 ... 1 bar g

(0 ... 14.5 psi g)

-0,4 bar g

(-5.8 psi g)

2 bar g

(30 psi g)

5 bar g

(72 psi g)

}

3 B A

0 ... 1.6 bar g

(0 ... 23.2 psi g)

-0,4 bar g

(-5.8 psi g)

3,2 bar g

(45 psi g)

5 bar g

(72 psi g)

}

3 B B

0 ... 2.5 bar g

(0 ... 36.3 psi g)

-0,8 bar g

(-11.6 psi g) 5 bar g

(72 psi g)

12 bar g

(175 psi g)

}

3 B D

0 ... 4 bar g

(0 ... 58.0 psi g)

-0,8 bar g

(-11.6 psi g) 8 bar g

(115 psi g)

12 bar g

(175 psi g)

}

3 B E

0 ... 6 bar g

(0 ... 87.0 psi g)

-1 bar g

(-14.5 psi g) 12 bar g

(175 psi g)

25 bar g

(360 psi g)

}

3 B G

0 ... 10 bar g

(0 ... 145 psi g)

-1 bar g

(-14.5 psi g) 20 bar g

(290 psi g)

50 bar g

(725 psi g)

}

3 C A

0 ... 16 bar g

(0 ... 232 psi g)

-1 bar g

(-14.5 psi g) 32 bar g

(460 psi g)

50 bar g

(725 psi g)

}

3 C B

0 ... 25 bar g

(0 ... 363 psi g)

-1 bar g

(-14.5 psi g) 50 bar g

(725 psi g)

120 bar g

(1750 psi g)

}

3 C D

0 ... 40 bar g

(0 ... 580 psi g)

-1 bar g

(-14.5 psi g) 80 bar g

(1150 psi g) 120 bar g

(1750 psi g)

}

3 C E

0 ... 60 bar g

(0 ... 870 psi g)

-1 bar g

(-14.5 psi g) 120 bar g

(1750 psi g) 250 bar g

(3600 psi g)

}

3 C G

0 ... 100 bar g

(0 ... 1450 psi g)

-1 bar g

(-14.5 psi g) 200 bar g

(2900 psi g) 450 bar g

(6525 psi g)

}

3 D A

0 ... 160 bar g

(0 ... 2320 psi g)

-1 bar g

(-14.5 psi g) 320 bar g

(4640 psi g) 450 bar g

(6525 psi g)

}

3 D B

0 ... 250 bar g

(0 ... 3626 psi g)

-1 bar g

(-14.5 psi g) 500 bar g

(7250 psi g) 650 bar g

(9425 psi g)

}

3 D D

0 ... 400 bar g

(0 ... 5802 psi g)

-1 bar g

(-14.5 psi g) 600 bar g

(8700 psi g) 650 bar g

(9425 psi g)

}

3 D E

Other version for measuring range

≥ 1 bar g (≥ 14.5 psi g), add Order code and plain text:

measuring range: ... up to... bar (psi g)

1)

9 A A

H 1 Y

For absolute pressure

0 ... 600 mbar a

(0 ... 8.7 psi a)

0 bar a

(0 psi a)

3 bar a

(43.5 psi a)

5 bar a

(72 psi a)

}

J)

5 A G 0

0 ... 1 bar a

(0 ... 14.5 psi a)

0 bar a

(0 psi a)

2 bar a

(30 psi a)

5 bar a

(72 psi a)

}

J)

5 B A

0 ... 1.6 bar a

(0 ... 23.2 psi a)

0 bar a

(0 psi a)

3,2 bar a

(45 psi a)

5 bar a

(72 psi a)

}

J)

5 B B

0 ... 2.5 bar a

(0 ... 36.3 psi a)

0 bar a

(0 psi a)

5 bar a

(72 psi a)

12 bar a

(175 psi a)

}

J)

5 B D

0 ... 4 bar a

(0 ... 58.0 psi a)

0 bar a

(0 psi a)

8 bar a

(115 psi a)

12 bar a

(175 psi a)

}

J)

5 B E

0 ... 6 bar a

(0 ... 87.0 psi a)

0 bar a

(0 psi a)

12 bar a

(175 psi a)

25 bar a

(360 psi a)

}

J)

5 B G

0 ... 10 bar a

(0 ... 145 psi)

0 bar a

(0 psi a)

20 bar a

(290 psi a)

50 bar a

(725 psi a)

}

J)

5 C A

0 ... 16 bar a

(0 ... 232 psi)

0 bar a

(0 psi a)

32 bar a

(460 psi a)

50 bar a

(725 psi a)

}

J)

5 C B

Other version for measuring range < 1 bar (< 14.5 psi a), add Order code and plain text:
measuring range: ... up to ... mbar a (psi a)

J)

9 A B 0

H 1 Y

}

Available ex stock

D) Subject to export regulations AL: N, ECCN: EAR99H.
J) Subject to export regulations AL: 9I999, ECCN: EAR99.

1)

The transmitters can also be ordered with special measuring ranges, e.g. the transmitter with the 1 bar measuring cell (14.5 psi measuring cell):
-0.2 ... +0.8 bar g (-2.9 ... +11.6 psi g) or
-0.4 ... +0.6 bar g (-5.8 ... +8.7 psi g) or ..., however start-of-scale value not under -0.4 bar g (-5.8 psi g), also see column "min. perm. operating pressure"

© Siemens AG 2008