6 Adjustments

6.9.4 Mode Switch (P/PI Switching)

6-64

(2) Operating Examples for Different Switching Conditions

Using the Torque Reference [Factory Setting]

With this setting, the speed loop is switched to P control when the value of torque reference input exceeds the

torque set in Pn10C. The factory setting for the torque reference detection point is 200% of the rated torque.

Using the Speed Reference

With this setting, the speed loop is switched to P control when the value of speed reference input exceeds the

speed set in Pn10D.

Using Acceleration

With this setting, the speed loop is switched to P control when the speed reference exceeds the acceleration set

in Pn10E.

Using the Position Error

With this setting, the speed loop is switched to P control when the position error exceeds the value set in

Pn10F.

This setting is effective with position control only.

Motor speed

Speed reference

Speed

+Pn10C

Torque
Reference

- Pn10C

Torque reference

PI Control

PI Control

0

PI

P

P

Time

Speed reference

Speed

Motor speed

Time

P Control

PI Control

Pn10D

PI

Motor

speed

Speed reference

Speed

Motor acceleration

+Pn10E

Acceleration

- Pn10E

PI Control

PI Control

0

PI

P

P

Time

Position
error

Speed reference

Speed

Motor speed

Time

P Control

PI Control

Pn10F

PI