1 me-ags-n setup (with the me-rtr) – Magnum Energy ME-RTR Router User Manual
Page 86

©
2014 Magnum Energy, Inc.
Page 78
Using an AGS Module: Setup
Autostart Condition
Autostop Condition
See Setup Menu
Page
Starts on low battery
voltage (DC voltage con-
nected to Terminals #3
and #4)
Stops on higher battery voltage
04A Gen Run DC Volts
79
Stops at Float Charge after a set
time period (using 03D Absorb
Done Time setting)
04A Gen Run DC Volts
(Set Stop Volts = Float)
79
Stops at Float Charge after bat-
tery current requirement is low
(using 03D Absorb Done Amps
setting)
04A Gen Run DC Volts
(Set Stop Volts = Float)
79
Stops at Float Charge using a
battery SOC setting (using 03D
Absorb Done SOC setting)²
04A Gen Run DC Volts
(Set Stop Volts = Float)
79
Starts at a set time daily Stops at a different set time daily
04B Gen Run Time
81
Starts on high AC amps
to an inverter load¹
Stops on lower AC amps to an
inverter load¹
04C Gen Run AC Amps
81
Starts when the battery
State of Charge (SOC)²
is low
Stops when the battery State of
Charge (SOC)² is higher
04D Gen Run SOC
82
Starts when temperature
increases
Stops after a set time period
04E Gen Run Temp
83
Note¹: Only applicable to MS-PAE, MS-PE, MSH-M and MSH-RE Series inverters.
Note²: Autostart/autostop conditions using SOC require the ME-BMK (battery monitor) to be
installed.
Table 7-2, ME-RTR Autostart/Autostop Matrix
7.1 ME-AGS-N Setup (with the ME-RTR)
To access the AGS SETUP menus, press and hold the METER button (~3 seconds) to display the
System Home screen. From the System Home screen, press the PORT button, or rotate the SELECT
knob to the port# where the AGS is connected (AGS Home screen), and then press the SETUP
button. The menus available from this screen allow the generator to be automatically started and
stopped based on many different conditions. From Table 7-2, determine the specifi c autostart and
autostop conditions with which you want to control the generator.
Info: The AGS SETUP menus can also be accessed by pressing the SETUP button from
the System Home screen, and rotating and pressing the SELECT knob after selecting
the 04 AGS Setup menu.