Magnum Energy ME-RTR Router User Manual
Page 54

©
2014 Magnum Energy, Inc.
Page 46
Setup
TECH: 08 Load all Defaults
This menu restores factory defaults to all settings on the inverter/charger and to any settings on
accessories that are networked. To restore, press and hold the rotary SELECT knob for 5 seconds
(“Resetting...” displays after 5 seconds). After the default settings have been restored, the display
will show “All Factory Default settings in all devices are loaded.” Refer to Table 3-3 for router
default values.
Info: For information on the factory default settings for any networked accessory, refer
to the owner’s manual for that accessory.
Info: If the PIN has been set and locked, it must be entered before the Load System
Defaults menu can be used.
Table 3-3, Inverter/Charger Default Settings on ME-RTR
Menu Items
Default Settings
Search Watts
5 Watts
LowBatCutOut
10 VDC (12v), 20 VDC (24v), 40 VDC (48v)
AC In – Time
Connect = 6:00AM, Disconnect = 6:00PM
AC In – Volts DC
Connect = 11.0V, Disconnect = 14.1V (12v)
Connect = 22.0V, Disconnect = 28.2V (24v)
Connect = 44.0V, Disconnect = 56.4V (48v)
AC In – SOC
Connect = 80%, Disconnect = 100%
Inv Always Power-up
NO
Inv Threshold to Start Parallel
60%
AC Input Amps
30 Amps (AC1), 20 Amps (AC2)*
Low VAC Dropout
80 VAC (AC1), 70 VAC (AC2)*, (Exports – 150 VAC)
Battery Type
Flooded
Absorb Done
Time = 2.0 Hrs
Max Charge
Rate = 100%, Time = 12.0 Hrs
Final Charge Stage
Multi-Stage
Days to remind EQ
OFF
* AC2 settings available on MSH4024RE models only
.