Using an AGS Module: Operation
Table 7-4, AGS Router Start Statuses
7.2.6.2
AGS Router Start Statuses
The following “Start” statuses identify the condition that autostarted the generator. If you determine
the autostart condition occurred sooner than expected (or didn’t want this autostart condition),
refer to Section 7.1 to change (or defeat) the autostart setting.
STATUS
DESCRIPTION
Start Amp
(StrtAmp or SAmp)
The generator has started based on the SETUP: 04C Gen Run AC
Amps settings.
Start Exercise
(StrtExe or SExe)
The generator has started based on the SETUP: 04H Gen Exercise
settings.
Start SOC
(StrtSOC or SSOC)
The generator has started based on the SETUP: 04D Gen Run
SOC setting.
Start Temp
(StrtTemp or STmp)
The generator has started based on the SETUP: 04E Gen Run
Temp setting.
Start Test
(StrtTest or STst)
The AGS is in Test mode. Test mode may be started from the
TEST button located on the AGS.
Start Time Daily
(StrtTOD or STOD)
The generator has started based on the SETUP: 04B Gen Run
Time setting.
Start Topoff
(StrtToff or STop)
The generator has started based on the SETUP: 04G Gen Quiet
Time menu’s Topoff time setting.
Start VDC
(StrtVDC or SVDC)
The generator either has started based on the SETUP: 04A Gen
Run Volts DC settings, or was manually started and then set to
AUTO to autostart.
Start 100% SOC
(Strt100% or S100)
The generator has started based on the SETUP: 04J Gen 100%
SOC settings.
7.2.6.3
AGS Router Fault Statuses
The following “Fault” statuses indicate that the generator wasn’t able to start based on an expected
autostart condition. Refer to Section 7.3.2 “Resolving AGS Faults using your Router” for help in
diagnosing the problem.
Table 7-5, AGS Router Fault Statuses
STATUS
DESCRIPTION
Fault Amp
(Falt Amp or FAmp)
The generator failed to start in Start Amps mode.
Fault Exercise
(Falt Exe or FExe)
The generator failed to start in Start Exercise mode.
Fault Gen Run
(FaltGnRn or FGnR)
The generator successfully started and ran for more than
two minutes, but unexpectedly stopped before the AGS could
automatically stop the generator.
Fault MaxRn
(FaltMxRn or FMxR)
The generator has run longer than expected and has met or
exceeded the SETUP: 04F Max Gen Run Time setting. This
fault can occur when: 1) an autostop condition has been met,
but the AGS was not able to stop the generator; or, 2) the
autostop setting exceeded the Max Gen Run Time setting.
Fault SOC
(Falt SOC or FSOC)
The generator failed to start in Start SOC mode.