Using an ags module: operation – Magnum Energy ME-RTR Router User Manual
Page 105

Page 97
©
2014 Magnum Energy, Inc.
Using an AGS Module: Operation
Auto Gen Start
Gen Ready 0.0Hrs
28.8VDC TS Open
P3 AGS Home
Inverting
Gen Ready
24.0VDC 12.0ADC
ALL System Home
System Home Screen – to access, press
and hold METER button for 3 sec
PORT
SETUP
04A Gen Run DC Volts
Start=23.0V/120secs
Stop =28.8V/120secs
P3 View AGS SETUP
Press PORT button until port# to
which AGS is connected appears
(i.e., AGS Home Screen)
Press SETUP button to access AGS
menus
Note: The AGS-N SETUP menus are accessed via the System Home screen and PORT button; or, by
pressing the SETUP button and rotating to the 04 AGS Setup menu, and then pressing the SELECT
knob. Refer to the procedures below to access these menu items via the AGS Home screen.
R
SETUP
Set Gen Run DC Volts
Start Volts = 23.0V
Stop Volts = 28.8V
P3 edit AGS SETUP
Set VDC Delay Times
Start Delay=120secs
Stop Delay =120secs
P3 edit AGS SETUP
04A Gen Run DC Volts
Start=23.0V/120secs
Stop =28.8V/120secs
P3 View AGS SETUP
04B Gen Run Time
OFF
P3 View AGS SETUP
Set Gen Run Time
Start Daily= OFF
Stop Daily =12:00AM
P3 edit AGS SETUP
04C Gen Run AC Amps
OFF
P3 View AGS SETUP
P
P
Start=OFF, 18.0-32.0
Stop=18.2-32.0, Float
R
P
OFF, 12:00AM-11:45PM
R
Set Gen Run AC Amps
Start AC Amps = OFF
Stop AC Amps = 4A
P3 edit AGS SETUP
P
Set Amps Delay Time
Start Delay=120secs
Stop Delay =120secs
P3 edit AGS SETUP
P
OFF, 4-60
0-127secs, 1-127mins
0-127secs, 1-127mins
Set Gen Run SOC
Start SOC = OFF
Stop SOC = 95%
P3 edit AGS SETUP
04D Gen Run SOC
OFF
P3 View AGS SETUP
04E Gen Run Temp
OFF
P3 View AGS SETUP
Set Gen Run Temp
Start Temp= OFF
P3 edit AGS SETUP
04F Max Gen Run Time
when Autostarted
= 12.0 Hours
P3 View AGS SETUP
P
R
P
R
Set Max Gen Run Time
when Autostarted
= 12.0 Hours
P3 edit AGS SETUP
P
OFF, 0.1-25.5
Start = OFF, ExtInput, 65F-95F
Run = 0.5-25.5 Hrs*
R
Start = OFF, 20-99%
Stop = 21-100%
x2
x2
* Shows if a start
temp selected
Figure 7-3, AGS SETUP Menu Maps (Section 1)