beautypg.com

6 mounting the router on a wall, 7 connecting the communication cables, Ab c d – Magnum Energy ME-RTR Router User Manual

Page 16

background image

©

2014 Magnum Energy, Inc.

Page 8

Installation

Cutout sections A-D to

accommodate routing

wires behind wall.

A

B

C

D

Figure 2-9, Mounting the Router to a Wall

2.6

Mounting the Router on a Wall

CAUTION: The router must be located close to the inverter/chargers (within six feet).

The router is designed to exchange data from the master inverter with one or multiple

slave inverters. The high speed communication data between the stack ports on the

router and the inverter ensure the slave inverters are synchronized to the master

inverter. To ensure the communications is not impacted, DO NOT exceed the 6-foot

stack cable distance between the router and each connected inverter.
Info: If a more distant monitoring location is required (more than six feet), a ME-RC50

or ME-ARC50 remote control may be connected and acts as a remote on/off switch to

assist in monitoring the system. See Section 9.0 for more information.

To mount the router on the surface of a wall:
1. Select an appropriate location to install the router (see Figures 2-2 & 2-3 for the router’s

dimensions).

2. Remove the router’s front cover, and then use the router bezel as a template to mark the

screw holes and the sections of the wall (or mounting surface) to remove to accommodate the

routing of the communication wires (Sections A-D on Figure 2-9).
Note: If you are not routing the communication wires thru the wall, there is no need to cut

sections from the wall.

3. Once the screw holes have been drilled and the optional wall sections are removed, mount the

router bezel to the wall using the 4 screws that are provided.

2.7 Connecting the Communication Cables

The stack and remote communication cables are used to connect each inverter/charger directly

to the router. A network cable is used to connect accessories to the router.
Each paralleled inverter/charger requires a high speed parallel stack cable connected to a stack

port on the router—marked MA (Master), SL1 (Slave 1), SL2 (Slave 2), and SL3 (Slave 3)—see

Figure 2-1. One inverter/charger will always be designated the “Master”, and subsequently any

other connected inverter/chargers are designated as “Slaves”. You can stack up to four MS-PAE

or MS-PE Series inverter/chargers using one router. It is recommended that you set up the Master

inverter as the fi rst unit on the left, and Slave 1 as the second unit, etc.