beautypg.com

3 secondary scrolling status messages – Magnum Energy ME-RTR Router User Manual

Page 70

background image

©

2014 Magnum Energy, Inc.

Page 62

Operation

5.3.3

Secondary Scrolling Status Messages

These displays alternate with the inverter’s primary status to indicate other pertinent messages.
Note: Depending on circumstances, the lighting sequence of the LED indicators may vary as there

can be several secondary status messages scrolling at any one time.

FAULT

PWR

CHG

INV

AC In - Disabled

Settings/Info...

AC In – Disabled appears on LCD. PWR (green) LED

is on solid and CHG (green) LED is blinking.

Figure 5-22, AC In – Disabled Mode

AC In – Disabled – AC power is present at the inverter’s AC input, but the inverter/charger

is prevented from connecting to any incoming AC because the AC In – Disabled setting is selected

from the CTRL: 01 AC In Control menu.

• Gen

Warm-up

– The ME-AGS-N has commanded a generator to run, but the inverter will not

connect to the generator’s AC output until the generator warm-up time is complete.
Note: Requires the optional ME-AGS-N Auto Gen Start module to be connected.

FAULT

PWR

CHG

INV

Max Charge Time

Settings/Info...

FAULT

PWR

CHG

INV

Gen Warm-up

Settings/Info...

Max Charge Time appears on LCD. PWR (green) LED

is on solid and CHG (green) LED is blinking.

Gen Warm-up appears on LCD. PWR (green) LED is

on solid and CHG (green) LED is blinking.

Figure 5-24, Max Charge Time Mode

Figure 5-23, Gen Warm-up Mode

Max Charge Time – This display indicates the Max Charge Time safety feature was enabled

because the charge time was longer than the Max Charge: Time setting.
If SETUP/03C Battery Type: CC/CV is selected: The charger was forced to transition to the Silent

charge stage because the charger had been in Constant Current and Constant Voltage charge

modes longer than the Max Charge: Time setting [under the Chg Done Time (or Amps) selection].
If SETUP/03C Battery Type: CC/CV is not selected: The charger was forced to transition to the

fi nal charge stage (Float, Silent, or Full Charge) as set under the SETUP button’s 03F Final Charge

Stage. This safety feature occurred because the charger had been in Bulk, Absorption, or EQ charge

modes longer than the Max Charge: Time setting.

Info: The Max Charge Time safety feature uses the time accumulated under the METER:

03A Charge Time display to determine the total charge time.

Info: The Max Charge: Time display can be reset by either reconnecting AC to the

inverter (causing the charge status to go to “Charging”), initiating another charge cycle

(Bulk, EQ, or Constant Current), or turning the Max Charge Time feature off.

Info: The timer for the Max Charge: Time menu runs when the battery voltage is

greater than 0.2 volts above the fl oat voltage setting.