1 how to clear ags faults – Magnum Energy ME-RTR Router User Manual
Page 112
©
2014 Magnum Energy, Inc.
Page 104
Using an AGS Module: Troubleshooting
7.3.2.1
How to Clear AGS Faults
To clear the AGS fault, go to the CTRL: 03 Gen Control menu and select OFF. Once the fault is
cleared, you should test the AGS/generator system by performing the AGS Functional Test—to
see if the fault returns.
Note: After troubleshooting the reason for the AGS fault, and then clearing the fault, be sure to
re-enable the AGS to autostart. Go to the CTRL: 03 Gen Control menu and select AUTO. Refer to
Figure 7-2.
• Fault
Topoff – The generator failed to autostart and run per the 04G Gen Quiet Time menu’s
Topoff start parameters.
• Fault
VDC – The generator failed to autostart and run per the 04A Gen Run Volts DC menu’s
start parameters.
• Fault 100% SOC – The generator failed to autostart and run per the 04J Gen 100% SOC
menu’s start parameters.
Remedy: One of the above fault messages may display on the router when:
a) The AGS attempts to start the generator four times, but the generator failed to start
and run per the specifi c autostart parameters; or,
b) The generator started, but did not provide the correct gen run sense signal to the
AGS module. For either scenario, refer to your AGS owner’s manual to troubleshoot why
the generator does not start or run.