Magnum Energy ME-RTR Router User Manual
Page 128

Appendix B – Compatibility Matrix
Page 120
Button
FEATURES/SETTINGS
Model/
Level
Required
Default
Setting
Main
Menu
Menu
Heading/Item
Selections/
Adjustments Range
SETUP
04 AGS
Setup
04A Gen Run DC
Volts
OFF, Start Volts= 9.0-15.9*
≥Level 1
11.5V
Start Delay= 0-127s, 1-127m
120 Secs
Stop Volts= 9.1-16.0*, Float
14.4V
Stop Delay= 0-127s, 1-127m
120 Secs
04B Gen Run Time
OFF, Start = 12:00A-11:45P
≥Level 1
OFF
Stop Daily = 12:00A-11:45P
12:00A
04C Gen Run AC
Amps
Start AC Amps = OFF, 5-60A
≥Level 4
OFF
Stop AC Amps = 4-59A
4A
Start Delay = 0-127s, 1-127m
120 sec
Stop Delay = 0-127s, 1-127m
120 sec
04D Gen Run SOC
OFF, Start SOC = 20-99%
≥Level 1
[6]
OFF
Stop SOC = 21-100%
90%
04E Gen Run Temp
Start = OFF, ExtInput, 65-95F
(18-35C)
≥Level 1
OFF
Time = 0.5-25.5 Hrs
65F/2 Hrs
04F Max Gen Run
Time
OFF, 0.1-25.5 Hrs
≥Level 1
12 Hrs
04G Gen Quiet Time
OFF, Begin = 12:00A-11:45P
≥Level 1
OFF
End Time = 12:00A-11:45P
10:00A
OFF, Topoff = 30-120 Mins
OFF
04H Gen Exercise
OFF, Days = 1-255 days
≥Level 1
OFF
Start Time = 12:00A-11:45P
8:00A
Run Time = 0.1-25.5 Hrs
1.0 Hrs
04I Gen No-Load
Time
Warm-up = 0-127s, 1-127m
≥Level 1
60 Secs
Cooldown = 0-127s, 1-127m
04J Gen 100% SOC
OFF, Days = 1-255
≥Level 1
[6]
OFF
Time = 12:00A-11:45P
8:00A
05 BMK
Setup
05A Charge Effi ciency Auto, 50-99%
≥Level 1
[6]
Auto
05B Battery AH Size
200-2500 AH
400 AH
06 Remote
Control
06A Remote Control
System, Port 1 – Port 6
≥Level 1
System
* – 12-volt values shown; multiply 12-volt values x2 for 24v systems, and x4 for 48v systems.
** – These settings return to the factory default setting when power to the router is removed.
[1] Not available on MM/MM-E/MM-AE/MMS/MMS-E Series models.
[2] AC Couple mode activates when Battery Type = Custom w/ MS-PAE Rev ≥4.1 or MS/MS-PE Rev ≥5.0.
[3] AC output volts only accurate when connected to MS, MS-PAE, MS-PE or MSH Series models.
[4] AC amps displays only appear when connected to MS-PAE, MS-PE, or MSH Series models.
[5] Level 2 and 3 inverters can be used, but: Level 2 inverters are limited from 1 to 4.5 hrs, Level 3 inverters
must be
and are limited from 1.5 to 6.5 hrs.
[6] BM/SOC features require the ME-BMK (Battery Monitor Kit) to be installed.
[7] ME-AGS-N Rev 5.2 or higher required to manually turn the generator “ON” with the router.