Using a BMK: Operation/Monitoring

8.2.4

BMK Status Messages (with the ME-RTR)

A status message may be an operational or fault message. Access the BMK Home screen (see

Section 8.1 to access) to view the BMK’s current operating status. The status is important when

determining if the BMK is working correctly, or for troubleshooting a BMK installation.

8.2.4.1

BMK Router Operational Statuses

Refer to Table 8-1 below for a brief description of the BMK operational statuses that may display

on your router.

Table 8-1, BMK Router Operational Statuses

STATUS

DESCRIPTION

No BMK

Present

The BMK is not communicating with the inverter/router. This is a normal status

if there is no BMK connected in the system.
If a BMK is installed, view the BMK sense module’s LED.
a) If the LED is green, disconnect the terminal block for 5 seconds, and then

reconnect it to ensure the terminal block is correctly seated into the sense

module.
b) If the LED is blinking red, there is no communication or there is an unrecognizable

communication on the network. Check the communication cable—ensure it is

connected correctly. If the ME-BMK communication cable is missing, a standard

2-conductor telephone cable may be temporarily substituted.

Think’n

(Thnk)

When the BMK Sense Module is first connected, the batteries need to be fully

charged (i.e., SOC = 100%) to establish a SOC reference point.
The BMK Sense Module is disconnected from power and the batteries require a full

charge before the router display begins providing SOC percentage information.

###%

(SOC:###%)

The batteries are fully charged, the display has changed from “Think’n” to

“100%” and is ready to provide accurate SOC percentage values.

8.2.4.2

BMK Router Fault Statuses

The following “Fault” statuses indicate that the battery monitor is not working correctly. Refer to

Section 8.3.2 “Resolving BMK Faults using the Router” for help in diagnosing the problem.

Table 8-2, BMK Router Fault Statuses

STATUS

DESCRIPTION

Factory Fault

(FacFault or FacF)

The BMK has lost its factory-set internal calibration reference.

Power-up Fault

(PwrFault or PwrF)

A fault occurred during the BMK’s power-up sequence.

Unknown Fault ##

(Fault## or F ##)

A fault code that is not recognized by the router.