Magnum Energy ME-RTR Router User Manual
Page 109

Page 101
©
2014 Magnum Energy, Inc.
Using an AGS Module: Operation
STATUS
DESCRIPTION
Fault Temp
(FaltTemp or FTmp)
The generator failed to start in Start Temp mode.
Fault Test
(FaltTest or FTst)
The generator failed to start in Test mode.
Fault Time Daily
(Falt TOD or FTOD)
The generator failed to start in Start Time mode.
Fault Topoff
(Falt Top or FTop)
The generator failed to start in Start Topoff mode.
Fault VDC
(Falt VDC or FVDC)
The generator failed to start in Start Volts DC mode.
Fault 100% SOC
(Falt100% or F100)
The generator failed to start in 100% SOC mode.
Table 7-5, AGS Router Fault Statuses (Cont.)
04 AGS SETUP MENUS
DEFAULT SETTINGS
04A Gen Run Volts DC
Start Volts = 11.5 VDC (12v), 23.0 VDC (24v), 46.0 VDC (48v)
Start Delay = 120 secs
Stop Volts = 14.4 VDC (12v), 28.8 VDC (24v), 57.6 VDC (48v)
Stop Delay = 120 secs
04B Gen Run Time
OFF
04C Gen Run AC Amps*
OFF
04D Gen Run SOC
OFF
04E Gen Run Temp
OFF
04F Max Gen Run Time
12.0 Hrs
04G Gen Quiet Time
OFF
04H Gen Exercise
OFF
04I Gen No-Load Time
Warm-up = 60 secs
Cooldown = 60 secs
04J Gen 100% SOC
OFF
*MS-PAE, MS-PE and MSH Series models only
Table 7-6, AGS Default Settings on ME-RTR