Output Registers
The following registers are used as outputs from the function block. They can be
monitored by the LadderWorks program to check the execution of the function.
Output Type
Description
RUNNING
Bit
High while block has control and move is in
progress.
ATVEL
Bit
This bit is ON when the Axis feedback speed
is at +/- 1% of the set speed.
ERROR
Bit
Latches high if any error occurs in block (see
table below) or on the servo axis (see IL**04).
Input Registers
The following registers are used as inputs to the function block. They select the options
and define the parameters that the user needs to make the function work as necessary.
Input
Type
Description
Range and state
EXECUTE Bit
Block enable – Block cannot
execute unless this is TRUE
Rising edge initiates block
TRUE – Block enable
FALSE – Block disable, set
all outputs to zero and off
AXIS
Word
Axis number related to the
block
1~16
DIRECTIO Word
Direction to travel
1 = Positive direction
2 = Negative direction
3 = Continue in current
direction.
VELOCITY Long
Speed in counts per second
to travel.
0 to Max. velocity (MW3**12)
in RDA
DATA07W
Address
Address of the first working
register.
Seven words of register
space are used by this
function.
File: MP2000_IndividualFunctionDocument_RevC 96/168
Doc Number: eng.MCD.05.101