TECHNICAL NOTE
The following table outlines several situations that may cause an error. The block error 
can be cleared by the EXECUTE bit going low 
Fault Bit
Cause
Note
axisInErr 
AB00000F 
The axis number 
entered on the 
input is not an 
acceptable value 
The function blocks can only control 1 to 
16axis. Any value greater or smaller then 
this will cause an error. This does not set 
the RDA Error ID. 
Notspec 
AB00000E 
Parameter 
specified is not a 
valid RDA number 
The number specified must be either the 
Yaskawa specified RDA area or the 
PLCOpen specified area. This block can 
not monitor Master/Slave data. Sets RDA 
Error ID (MW3**81) bit 3 on if error state 
exists. 
valueOut 
AB00000D 
Value out of range 
for the RDA 
Value must be within range of value being 
stored or error will occur. Sets RDA Error 
ID (MW3**81) bit 3 on if error state exists. 
 
 
This table outlines the data in the six registers used by the function block. There is not 
usually any need for the user to access any of these bits directly. 
Register No
TYPE
Name
Content
AW00000
Working
Reserved
Reserved
AW00001
Working
Reserved
Reserved
AW00002
Working
iStore
Reserved
AW00003
Working
ivalue
Reserved
AW00004
Working
rdaMult
Value for address offset to locate proper RDA
AW00005
Working
Revision
Revision Level of the function block.
File: MP2000_IndividualFunctionDocument_RevC 150/168 
Doc Number: eng.MCD.05.101 
11/17/2005