Change dynamics function, Chngdyn> function block summary, Chngdyn> function block operation notes – Yaskawa MP2000 User Manual
Page 30: Chng_dyn

TECHNICAL NOTE
File: MP2000_IndividualFunctionDocument_RevC 30/168
Doc Number:
EF.MCD.05.101
11/17/2005
CHANGE DYNAMICS function
Function block for MP2000 series
This function block sets acceleration, deceleration, S-Curve and the speed. Each parameter is set in the
first execution scan.
Function Block Diagram
• Rising edge of EXECUTE input initiates block operation, and all block input
values are read once.
• To use the function block, the EXECUTE bit must be held ON. If the EXECUTE
bit goes off during operation, the block will finish move but all outputs will be set
to zero.
• The
RUNNING
output bit will be held high parameter change is completed,
EXECUTE
goes low or an Error occurs.
• If any of the inputs (absolute value) are greater then the Maximum value in the
RDA an Error will occur.
• When parameter setting is completed, the DONE output is turned on.
• Each value (SPEED, ACCEL, DECEL, and SCURVE) is also set to the
corresponding RDA.
• S-Curve value is for the running average filter. S-curve outputs literally “S"
reference on acceleration and the deceleration.