TECHNICAL NOTE
Output Registers
The following registers are used as outputs from the function block. They can be
monitored by the LadderWorks program to check the execution of the function.
Output Type
Description
RUNNING
Bit
High while block has control and move is in progress.
DONE
Bit
Turns on when Homing process is completed
ERROR
Bit
Latches high if any error occurs in block (see table
below) or on the servo axis (see IL**04).
Input Registers
The following registers are used as inputs to the function block. They select the options
and define the parameters that the user needs to make the Home function work as
necessary.
Input
Type
Description
Range and State
EXECUTE
Bit
Block enable – Block cannot
execute unless this is TRUE.
Rising edge initiates block
TRUE – Block enable
FALSE – Block disable, set all
outputs to zero and off
REVERSE
Bit
Determines direction of homing.
TRUE – Seek in reverse
FALSE – Seek in forward
INPUT
Bit
“INPUT” signal for Homing type
that uses it.
Only homing type 18 and 19 use
the INPUT signal.
AXIS
Word
Axis number related to the block
1~16
TIME
Word
Maximum time to complete the
homing, if timeout then ERROR.
Time in seconds.
Range: 0 to 32767 integers
TRAVSPD
Long
Traverse speed of servo while
searching for the home switch. In
counts per second.
0 to maximum speed (ML3**12)
APRSPD
Long
Approach speed reference
unit/sec
0 to maximum speed (ML3**12)
CRPSPD
Long
Creep rate reference unit/sec
0 to maximum speed (ML3**12)
Offset
Long
Final moving distance. And the
position will be this value.
Position in encoder counts.
Range –2
31
to 2
30
integers
DATA11W
Address
Address of the first working
register.
Eleven words of register space are
used by this function.
File: MP2000_IndividualFunctionDocument_RevC 45/168
Doc Number: eng.MCD.05.101