SERVICE MANUAL TNC

Issue:

01.09.1995

Page

81

17.2.2 PLC Outputs

Check the PLC outputs as follows:

Connect the test unit between LE and PLC or between LE and PL.
Set the TNC as follows:

Prepare TNC for code number input

Enter code number, acknowledge with ENT

Soft key

to display the tables

Soft key

to display the output table

Now the logic states of the outputs are displayed on the screen. The states of the screen display must

correspond to those of the test unit. If there is a difference, test the connecting cable for short circuit and

measure the output current at interface (max. 100

for LE outputs, max. 1.2 A for PL outputs). If the

output current is not exceeded and the connecting cable is in order, the output board is probably defective

(00 to 030 of processor board, 032 to 062 of

board PL 400).

switch TNC back to operating

NOTE:
Always switch off the main switch before engaging or disengaging any connector.