Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-59

This parameter sets the Ac drive address identification when using the RS-485 serial port for

communication.

Pr.89

Transmission Speed (Baud rate)

Factory Setting: 01

Settings

00

4800

bps

01

9600

bps

02

19200

bps

03

38400

bps

This parameter sets the transmission speed for communication on the RS-485 serial port

Pr.90

Transmission Fault Treatment

Factory Setting: 03

Settings 00 Warn and Continue Operating

01 Warn and RAMP to Stop

02 Warn and COAST to Stop

03 Keep Operation without Warning

Pr.91

Time Out Detection

Factory Setting: 0.0

Settings 0.1 to 120.0 sec

0.0

disable

This parameter is used for ASCII mode. When the over-time detection is enabled, the

separation between characters cannot exceed 500 ms.

Pr.92

Communication Protocol

Factory Setting: 00

Settings

00

Modbus

ASCII mode, <7,N,2>

01 Modbus ASCII mode, <7,E,1>

02 Modbus ASCII mode, <7,O,1>

03 Modbus RTU mode, <8,N,2>

04 Modbus RTU mode, <8,E,1>

05 Modbus RTU mode, <8,O,1>

1. Computer Control