beautypg.com

Delta Electronics VFD-M User Manual

Page 76

background image

Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-41

Pr.45

Multi-function Output Terminal 1 (Photocoupler output)

Factory Setting: 00

Pr.46

Multi-function Output Terminal 2 (Relay output)

Factory Setting: 07

Settings 00 to 24

Settings

Function

Description

00

AC Drive Operational

Terminal output is activated when there is power output

from drive.

01

Maximum Output

Frequency Attained

Terminal output is activated when the AC drive attains

Maximum Output Frequency.

02 Zero

speed

Terminal output is activated when Command Frequency is

lower than the Minimum Output Frequency.

03 Over-Torque

detection

Terminal output is activated when over-torque is detected.

Parameter Pr.61 determines the Over-Torque detection

level.

04

Base-Block (B.B.)

Indication

Terminal output is activated when the AC drive output is

shut-off by the external Base-Block.

05

Low-Voltage Indication

Terminal output is activated when low voltage is detected.

06

AC Drive Operation Mode

Terminal output is activated when the operation of AC Drive

is controlled by External Control Terminals.

07 Fault

Indication

Terminal output is activated when certain faults occur (oc,

ov, oH, oL, oL1, EF, cF3, HPF, ocA, ocd, ocn, GF).

08

Desired Frequency

attained

Terminal output is activated when the desired frequency

(Pr.47) is attained.

09

PLC Program Running

Terminal output is activated when the PLC program is

running.

10

PLC Program Step

Completed

Terminal output is activated for 0.5 sec. when each multi-

step speed is attained.

11

PLC Program Completed

Terminal output is activated for 0.5 sec. when the PLC

program cycle has completed.

12

PLC Operation Paused

Terminal output is activated when PLC operation is paused.

13

Top Count Value Attained

Terminal output is activated when counter reaches the Top

Count Value. See diagram for Pr.38 to Pr.42=18.