Chapter 4 Parameters|

4-46

Revision May 2008, ME14, SW V3.04

Example 5:

In this example, a 6 Hz (10% of 60 Hz) negative bias is used. This setting is used to provide a noise

margin (1V in this example) in noisy environments. Note that the top frequency is reduced to 54 Hz.

Max.
Output

Freq.

60Hz

Pr.03

0Hz

0V

10V

Factory Settings

Pr.03=60Hz--Max. output Freq.
Pr.48=10.0% -- bias adjustment

Pr.49=1 -- bias polarity
Pr.50=100% -- pot. freq. gain

Pr.51=0 -- Rev. motion disable
in negative bias

Negative
bias 6Hz

1V

54Hz

Hz

0V

10V

24

0

54

Potentiometer Scale

It's 0Hz
within
this
range.

Example 6:

This example also uses negative bias and includes a potentiometer frequency gain to allow the AC

drive to reach the Maximum Output Frequency.

Max.
Output
Freq.

60Hz

Pr.03

0Hz

0V

10V

Factory Settings

Pr.03=60Hz--Max. output Freq.

Pr.48=10%--bias adjustment
Pr.49=1 -- bias polarity

Pr.50=111% -- pot. freq. gain
Pr.51=0 -- REV. motion disable
in negative bias

Negative
bias 6.6Hz

1V

Hz

0V

10V

27

0

60

Potentiometer Scale

It's 0Hz
within
this
range.

Bias adjustment

Calculation of gain

Pr.50=( 10V

9V

)X100%=111%

Example 7:

In this example, the potentiometer is programmed to run a motor in forward or reverse direction. The

motor will idle when the potentiometer is set at the scale mid-point. Please note that this adjustment

will disable the external FWD and REV controls.

Max.Output Freq.

Pr.03

Factory Settings

Pr.03=60Hz--Max. output Freq.
Pr.48=50%--bias adjustment

Pr.49=1 -- bias polarity
Pr.50=200% -- pot. freq. gain

Pr.51=1 -- REV motion disable
in negative bias

60Hz

30Hz

0Hz

0V

5V

10V

30Hz

60Hz

REV

FWD

Hz

0V

10V

0

60

60

Potentiometer Scale

REV.

FWD.