Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-27

Pr.24

Reverse Operation Inhibition

Factory Setting: 00

Settings 00 Enable REV operation

01 Disable REV operation

This parameter is used to disable motor rotation in reverse.

Pr.25

Over–Voltage Stall Prevention

Settings 115V/230V series

330-450Vdc

Factory Setting: 390

460V series

660-900Vdc

Factory Setting: 780

575V series

825-1025Vdc

Factory Setting: 975

00

disable

During deceleration, the DC bus voltage may exceed its maximum allowable value due to

motor regeneration. When this function is enabled, the AC drive will stop decelerating, and

maintain a constant output frequency to prevent from over-voltage tripping. Drive will resume

deceleration when the voltage drops below the setting for Pr.25.

Note: In applications where inertia is low, over-voltage during deceleration would not occur. When

inertia is high, the AC drive will automatically extend the deceleration period. If a faster stop is

needed, then a dynamic brake resistor should be used.

DC bus voltage

time

Over-voltage
detection

level

output

Freq.

time

Over-voltage Stall Prevention

Pr.26

Over-Current Stall Prevention during Acceleration

Unit: 1%

Factory Setting: 150%

Settings 20 to 200%

00

disable

A setting of 100% is equal to the Rated Output Current of the drive.