Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-75

Pr.105

Control Mode

Factory Setting: 00

Settings

00

V/F

Control

01

Sensor-less

Control

Pr.106

Rated Slip

Unit: 0.01Hz

Settings 0.00 to 10.00 Hz

Factory Setting: 3.0

Example of Slip calculation: The rated speed of 4 poles/3

φ/ 60Hz/ 220V on the nameplate is

1710RPM. The rated slip is then: 60-(1710/(120/P))=3Hz. (being P the number of poles)

Pr.107

Vector Voltage Filter

Unit: 2ms

Settings 5 to 9999

Factory Setting: 10

Pr.108

Vector Slip Compensation Filter

Unit: 2ms

Settings 25 to 9999

Factory Setting: 50

This parameter sets the low-pass filter in vector control.

Example: Pr. 107 = 10 X 2ms =20ms, Pr. 108 = 50 X 2 ms =100ms.

Pr.109

Selection for Zero Speed Control

Factory Setting: 00

Settings

00

No

output

01 Control by DC voltage

This parameter is used to select the control method at zero speed. If set to 01, the voltage in

Pr.110 is used for holding torque.

Pr.110

Voltage of Zero Speed Control

Unit: 0.1%

Settings 0.0 to 20.0 % of Max. output voltage (Pr.05)

Factory Setting: 5.0

This parameter should be used in conjunction with Pr.109.

Example: if Pr.05 = 100 and this parameter is set to 20.0, the level of output voltage is

100X20.0% = 20.

Pr.111

Deceleration S Curve

Settings 00 to 07

Factory Setting: 00

When this parameter is set differently to zero, it selects a deceleration S-curve and overrides

Pr.14. Otherwise, Pr.14 sets the deceleration S-curve.