Chapter 4 Parameters|

4-52

Revision May 2008, ME14, SW V3.04

Carrier Frequency

Acoustic Noise

Electromagnetic Noise,

Leakage Current

Heat Dissipation

1KHz

15KHz

Significant

Minimal

Minimal

Significant

Minimal

Significant

From the above table, we see that the carrier frequency of PWM output has a significant

influence on the electromagnetic noise, heat dissipation of the AC drive, and the acoustic

noise to the motor.

Pr.72

Auto Restart Attempts After Fault

Settings 00 to 10

Factory Setting: 00

When this parameter is enabled (set different to zero), the AC Drive will restart/reset

automatically up to 10 times after the occurrence of certain type of faults (over-current OC,

over-voltage OV). If enabled, the AC drive will restart on “speed search”, which begins at

Master Frequency. Setting this parameter to 0 will disable this operation. To set the fault

recovery time after a fault, please see base-block time for speed search (Pr.34).

Pr.73

Present Fault Record

Pr.74

Second Most Recent Fault Record

Pr.75

Third Most Recent Fault Record

Factory Setting: 00

Settings 00 (no fault occurred )

01

Over-current

(oc)

02

Over-voltage

(ov)

03

Overheat

(oH)

04

Overload

(oL)

05 Overload 1 (oL1)

06 External Fault (EF)

07 CPU failure 1 (CF1)

08 CPU failure 3 (CF3)

09 Hardware Protection Failure (HPF)

10 Over-current during acceleration (OCA)

11 Over-current during deceleration (OCd)

12 Over-current during steady state operation (OCn)