Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-43

Pr.47

Desired Frequency Attained

Unit: 0.1Hz

Settings 0.00 to 400.0 Hz

Factory Setting: 0.00

This parameter allows monitoring a certain frequency and then activates one of the Multi-

function output terminals (Pr.45 or Pr.46 set to 8) when that frequency is achieved.

Desired Freq.

Detection

range

-2Hz

Detection
range

+

-

4Hz

Detection range

+

-

2Hz

Time

Freq.

Max. Output
Freq.

ON

ON

OFF

OFF

OFF

OFF

Preset Freq.
Attained
Indication
Pr.45 to
Pr.46

Desired Freq.
Attained
Indication
Pr.45 & Pr.46

Desired Freq. Attained & Preset Freq. Attained

Pr.47

Pr.48

Adjust Bias of External Input Frequency

Unit: 0.1Hz

Settings 0.00 to 200.0%

Factory Setting: 0.00 Hz

This parameter provides a frequency offset when the source of frequency command is the

analog input.

Pr.49

Potentiometer Bias Polarity

Factory Setting: 00

Settings

00

Positive

Bias

01

Negative

Bias

This parameter sets the potentiometer Bias Frequency to be positive or negative.

Pr.50

Potentiometer Frequency Gain

Unit: 1%

Settings 0.10 to 200.0%

Factory Setting: 100.0

This parameter sets the ratio of analog input vs frequency output.

Pr.51

Potentiometer Reverse Motion Enable

Factory Setting: 00

Settings 00 Reverse Motion Disabled in negative bias

01 Reverse Motion Enabled in negative bias