Chapter 4 Parameters|

4-38

Revision May 2008, ME14, SW V3.04

Settings

Function

Description

18

Counter Trigger Signal

Parameter value 18 programs Multi-Function Input Terminal:

M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)

to increase the AC drive’s internal counter. When an input is

received, the counter is increased by 1.

GND

18 counter

trigger signal
input.

Mx counter value increase by

1 when closed.

Trigger

Note: The Counter Trigger input can be connected to an

external Pulse Signal Generator when counting a

process step or unit of material. See the diagram

below.

2ms

2ms

Indication value

(Pr.64=1)

Counter trigger signal

Multi-function input terminal

Signal output with Pr.97

counter value is attained.

(Pr.97=3)

(Pr.45/46=13)

Signal output with Pr.96
counter value is attained.

(Pr.96=5)

(Pr.45/46=14)

The trigger timing
can't be less than
2ms.(<250Hz)

(Pr.38 to Pr.42 =18)

19 Counter

Reset

Parameter value 19 programs Multi-Function Input Terminal:

M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)

to reset the counter.

GND

19 reset the
counter value.

Mx "close": reset counter.

Reset counter

20 No

Function

Enter value (20) to disable any Multi-Function Input Terminal:

M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)

Note: Purpose of this function is to isolate unused Multi-

Function Input Terminals. Any unused terminals should

be programmed to 20 to insure they have no effect on

drive operation.