Delta Electronics VFD-M User Manual

Page 44

background image

Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-9

Parameter

Explanation

Settings

Factory

Setting

Customer

Pr.78

PLC Operation Mode

00: Disable PLC operation
01: Execute one program cycle
02: Continuously execute program cycles
03: Execute one program cycle step by step
04: Continuously execute one program cycle

step by step

00

Pr.79

PLC FWD/REV
Motion

00 to 127

00

Pr.80

Identity Code of the
AC Motor Drive

Read only

##

Pr.81

Time Duration of 1st
Step Speed

00 to 9999 sec

00

Pr.82

Time Duration of 2nd
Step Speed

00 to 9999 sec

00

Pr.83

Time Duration of 3rd
Step Speed

00 to 9999 sec

00

Pr.84

Time Duration of 4th
Step Speed

00 to 9999 sec

00

Pr.85

Time Duration of 5th
Step Speed

00 to 9999 sec

00

Pr.86

Time Duration of 6th
Step Speed

00 to 9999 sec

00

Pr.87

Time Duration of 7th
Step Speed

00 to 9999 sec

00

Pr.88

Communication
Address

01 to 254

01

Pr.89 Transmission

Speed

00: 4800 bps
01: 9600 bps
02: 19200 bps
03: 38400 bps

01

Pr.90

Transmission Fault
Treatment

00: Warn and Continue Operating
01: Warn and RAMP to Stop
02: Warn and COAST to Stop
03: Keep Operation without Warning

03

Pr.91

Time Out Detection

0.0: Disable
0.1 to 120.0 sec

0.0

Pr.92

Communication
Protocol

00: MODBUS ASCII mode, <7,N,2>
01: MODBUS ASCII mode, <7,E,1>
02: MODBUS ASCII mode, <7,O,1>
03: MODBUS RTU mode, <8,N,2>
04: MODBUS RTU mode, <8,E,1>
05: MODBUS RTU mode, <8,O,1>

00