Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-83

When Line Start Lockout is disabled (also known as Auto-Start), the drive will start when

powered-up with run commands applied. To start in Line Start Lockout mode, the AC drive

must see the run command go from stop to run after power up. When enabled, the AC drive

will not start when powered up if run commands were applied.

Pr. 147

Decimal Number of Accel / Decel Time

Factory Setting: 00

Settings

00

One

Decimal

01

Two

Decimals

It sets the number of decimals in the accel/decel time. It can be used for Acceleration /

Deceleration Time 1, Acceleration / Deceleration Time 2 and JOG Acceleration / Deceleration

Time.

Pr. 148

Number of Motor Poles

Settings 02 to 20

Factory Setting: 04

Pr. 149

Gear Ratio for Simple Index Function

Settings 4 to 1000

Factory Setting: 200

Pr. 150

Index Angle for Simple Index Function

Settings 00.0 to 360.0

Factory Setting: 180.0

Pr. 151

Deceleration Time for Simple Index Function

Factory Setting: 0.00

Settings 0.00 to 100.00 sec

0.00

Disable

This parameter should be used with Pr. 39-Pr.42 (setting 31).