Appendix CHow to Select the Right AC Motor Drive|

C-4

Revision May 2008, ME14, SW V3.04

C.2 General Precaution

Selection Note

1、

When the AC Motor Drive is connected directly to a large-capacity power transformer

(600kVA or above) or when a phase lead capacitor is switched, excess peak currents

may occur in the power input circuit and the converter section may be damaged. To

avoid this, use an AC input reactor (optional) before AC Motor Drive mains input to

reduce the current and improve the input power efficiency.

2、

When a special motor is used or more than one motor is driven in parallel with a single

AC Motor Drive, select the AC Motor Drive current

≥1.25x(Sum of the motor rated

currents).

3、

The starting and accel./decel. characteristics of a motor are limited by the rated current

and the overload protection of the AC Motor Drive. Compared to running the motor

D.O.L. (Direct On-Line), a lower starting torque output with AC Motor Drive can be

expected. If higher starting torque is required (such as for elevators, mixers, tooling

machines, etc.) use an AC Motor Drive of higher capacity or increase the capacities for

both the motor and the AC Motor Drive.

4、

When an error occurs on the drive, a protective circuit will be activated and the AC

Motor Drive output is turned off. Then the motor will coast to stop. For an emergency

stop, an external mechanical brake is needed to quickly stop the motor.

Parameter Settings Note

1、

The AC Motor Drive can be driven at an output frequency up to 400Hz (less for some

models) with the digital keypad. Setting errors may create a dangerous situation. For

safety, the use of the upper limit frequency function is strongly recommended.

2、

High DC braking operating voltages and long operation time (at low frequencies) may

cause overheating of the motor. In that case, forced external motor cooling is

recommended.

3、

Motor accel./decel. time is determined by motor rated torque, load torque, and load

inertia.

4、

If the stall prevention function is activated, the accel./decel. time is automatically

extended to a length that the AC Motor Drive can handle. If the motor needs to