beautypg.com

Delta Electronics VFD-M User Manual

Page 112

background image

Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-77

P

Pr.117

I

Pr.118

D

Pr.119

Pr.120

AVI(

)

ACI(

)

Pr.128~Pr.130

Pr.131~Pr.133

Pr.116

+

-

+

+

Pr.135

LPF

Targeted

value

Upper Bound
of Integral
Value

Pr.122

+

Limit of PID
Output
Frequency

One Time
Delay

Pr.121

Definition of

Detection Value

Frequency

Command

Selection of
Detection value

Pr. 116

PID Feedback Terminal Selection

Factory Setting: 00

Settings 00 Input positive PID feedback, PV from AVI (0 to 10V)

01 Input negative PID feedback, PV from AVI (0 to 10V)

02 Input positive PID feedback, PV from ACI (4 to 20mA)

03 Input negative PID feedback, PV from ACI (4 to 20mA)

Select an input terminal to be the PID feedback. Please verify the PID feedback position is

different from the Frequency Set Point position.

Negative feedback = positive targeted value – detective value. Positive feedback = negative

targeted value + detective value.

Pr. 117

Proportional Gain (P)

Settings 0.0 to 10.0

Factory Setting: 1.0

This parameter determines the feedback loop Gain. If the gain is large, the response will be

strong and immediate (If the gain is too large, vibration may occur). If the gain is small, the

response will be weak and slow.

When I=0.0 and D=0.0, it is only used for proportional control.

Pr. 118

Integral Time (I)

Unit: 0.01sec

Factory Setting: 1.00

Settings 0.01 to 100.00 sec

0.00

disable

This parameter determines the speed of response for the PID feedback loop. If the integral

time is long, the response will be slow. If the integral time is short, the response will be quick.

Be careful not to set (I) too small, since a rapid response may cause oscillation in the PID loop.