Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-39

Settings

Function

Description

21 RESET

Command

(N.C)

22

Control source: External

Terminal

23

Control source: Keypad

24

Control source:

Communication

Enter values 22, 23, or 24 to set the control source to be the

external terminals, keypad or communication respectively.

This setting is used to create functions for manual/auto, and

remote/near-end control. When these three functions are

used at the same time, the priority is 22-I/O > 23-Keypad >

24-Communication.

25

Parameter Lock (Write

disable, Read is always

0)

This function will disable the write function and all the content

of read are 0. The application is for customer having a key to

control the operator to modify parameters or modify the

parameter by improper use.

26

PID Disable (N.O.)

27

PID Disable (N.C.)

This function pause the PID control. It is commonly used for

manual operation or function testing, and to recover the PID

function when the system is normal.

28

Second Source for

Frequency Command

This function is used with Pr. 142 to select a different

frequency source for control.

29

Forward (contact is

open) / Reverse (contact

is close)

This function has top priority to set the direction for running (If

“Pr. 24 inhibit REV function” is not set). No mater what the

present direction of run is, the contact N.O. is forward and the

contact N.C. is reverse, once this function is set.

The requirement for setting direction is Pr. 24 > setting 29 of

Pr. 39-Pr. 42 > Pr. 38.

30

One-Shot PLC Run

31 Index

Input

Signal

This function is used with parameters 149 to 151. The position

where AC drive stops will be regarded as the zero position

and it will move to the angle that Pr. 150 sets.

32 Virtual

Timer

Input

This function is for counting at the speed of the output

frequency.

Note: The settings 00~32 in Pr. 39 to Pr.42 can be used to set multi-function terminals (M2-M5) but

the settings cannot be used repeatedly at the same time (besides settings 20).